HARTFORD, CT —
OSHA Inspection: ALL WASTE INCORPORATED
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ALL WASTE INCORPORATED in 35 MAXIM ROAD, HARTFORD, CT 06114 (NAICS 562111). OSHA activity number 347471591.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALL WASTE INCORPORATED
- Site address
- 35 MAXIM ROAD
- City
- HARTFORD
- State
- CT
- ZIP
- 06114
- Mailing
- 143 MURPHY ROAD, HARTFORD, CT 06114
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 562111
- Employees
- 8
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.157 E03
- Issued
- Jun 7, 2024
- Penalty
- Initial $5,288 · Current $3,702 Reduced
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: Main Bay: On, or about, May 9, 2024, portable fire extinguishers located near the electrical panels had tags that indicated the last inspection had been conducted in 2019.
Recent events (2)
- — I (S) $3701.6
- — Z (S) $5288
1910.157 G04
- Issued
- Jun 7, 2024
- Abate by
- Jul 26, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(4): Employees who have been designated to use firefighting equipment as a part of the emergency action plan were not provided training in the use of appropriate equipment upon initial assignment and at least annually thereafter: Company: On, or about, May 9, 2024, employees who used portable fire extinguishers had not been provided with training since September, 2018.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Jun 7, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Main Bay: On, or about, May 9, 2024, boxes and fire extinguishers were stored in front of two wall mounted electrical panels, a General Electric and an Empire.
Recent events (2)
- — I (O) $0
- — Z (O) $0