Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALL WASTE INCORPORATED

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ALL WASTE INCORPORATED in 35 MAXIM ROAD, HARTFORD, CT 06114 (NAICS 562111). OSHA activity number 347471591.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ALL Waste Incorporated — free Get an email when a new federal OSHA severe-injury report for ALL Waste Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
35 MAXIM ROAD
City
HARTFORD
State
CT
ZIP
06114
Mailing
143 MURPHY ROAD, HARTFORD, CT 06114
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562111
Employees
8
Ownership type
A

3 citations on file for this inspection.

1910.157 E03

Serious Gravity 1 7 instances 8 exposed
Issued
Jun 7, 2024
Penalty
Initial $5,288 · Current $3,702 Reduced
29 CFR  1910.157(e)(3):  Portable fire extinguishers were not subjected to an annual maintenance check:  Main Bay:  On, or about, May 9, 2024, portable fire extinguishers located near the electrical panels had tags that indicated the last inspection had been conducted in 2019.
Recent events (2)
  • — I (S) $3701.6
  • — Z (S) $5288

1910.157 G04

Serious Gravity 1 1 instance 8 exposed
Issued
Jun 7, 2024
Abate by
Jul 26, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.157(g)(4):  Employees who have been designated to use firefighting equipment as a part of the emergency action plan were not provided training in the use of appropriate equipment upon initial assignment and at least annually thereafter:  Company:  On, or about, May 9, 2024, employees who used portable fire extinguishers had not been provided with training since September, 2018.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Other-than-serious 1 instance 8 exposed
Issued
Jun 7, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):  The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Main Bay:  On, or about, May 9, 2024, boxes and fire extinguishers were stored in front of two wall mounted electrical panels, a General Electric and an Empire.