WYNCOTE, PA —
OSHA Inspection: B POSITIVE PLASMA NATIONAL BLOOD SERVICES LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of B POSITIVE PLASMA NATIONAL BLOOD SERVICES LLC in 2385 WEST CHELTENHAM AVENUE SUITE 310, WYNCOTE, PA 19095 (NAICS 621991). OSHA activity number 347483240.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- B POSITIVE PLASMA NATIONAL BLOOD SERVICES LLC
- Site address
- 2385 WEST CHELTENHAM AVENUE SUITE 310
- City
- WYNCOTE
- State
- PA
- ZIP
- 19095
- Mailing
- 2385 WEST CHELTENHAM AVENUE SUITE 310, WYNCOTE, PA 19095
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 621991
- Employees
- 30
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 G01
- Issued
- Nov 14, 2024
- Abate by
- Dec 4, 2024
- Penalty
- Initial $5,288 · Current $3,966 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) 2385 W Cheltenham Ave Suite 310, Wyncote, PA 19095 - SE Storage Room - On or about May 15, 2024, a 220 volt electrical panel was blocked by multiple storage boxes that reduced work space to 19 inches from the face of the panel. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3966
- — Z (S) $5288
1910.132 D02
- Issued
- Nov 14, 2024
- Abate by
- Dec 4, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2): The employer did not verify, through a written certification, the identity of the workplace evaluated, the person certifying that the evaluation had been performed, and the date the hazard assessment was done: a) 2385 W Cheltenham Ave Suite 310, Wyncote, PA 19095 - On or about May 15, 2024, the employer did not document through a written certification, that a required workplace hazard assessment had been performed in accordance with this section. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states that employees and their representatives were informed of this abatement.