OSHA Inspection: AMPERSAND NEW YORK OPERATIONS CO, LLC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of AMPERSAND NEW YORK OPERATIONS CO, LLC in 510 CONGRESS ST, TROY, NY 12180 (NAICS 221111). OSHA activity number 347494056.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ampersand NEW York Operations CO, LLC — free Get an email when a new federal OSHA severe-injury report for Ampersand NEW York Operations CO, LLC is published. One employer, no account, unsubscribe in one click.
Site address
510 CONGRESS ST
City
TROY
State
NY
ZIP
12180
Mailing
717 ATLANTIC AVE, BOSTON, MA 02111
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
221111
Employees
16
Ownership type
A

12 citations on file for this inspection.

1910.269 A02 I A

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(a)(2)(i)(A): Each employee was not trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments:  (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not provide training or ensure familiarity with the necessary safety-related work practices, procedures, and other safety requirements relevant to this job assignment. Including but not limited to safe work procedures, identification and recognition of arc flash hazards, and use of arc flash protective clothing.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

1910.269 B

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $6,452 · Current $6,452
29 CFR  1910.269(b):The employer did not provide medical services and first aid as required in 1910.151:  (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized breaker cell during racking-in.  The employer did not provide medical services to render first aid in case of an emergency in that none of the personnel on the jobsite were trained in first aid or CPR, and the employer made no other provisions to provide them.
Recent events (2)
  • — C (S) $6452
  • — Z (S) $6452

1910.269 C01 II

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $6,452 · Current $6,452
29 CFR  1910.269(c)(1)(ii):The employer did not ensure that the employee in charge conducted a job briefing that met paragraphs (c)(2) though (c)(4) of this section with the employees involved before they start each job:  (a) Mount Ida Hydro Station, Control room level:  On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized breaker cell during racking-in. The employer did not ensure that the employee in charge conducted a job briefing with the employees the covered the hazards associated, work to be performed, energy controls, PPE requirements and special precautions.
Recent events (2)
  • — C (S) $6452
  • — Z (S) $6452

1910.269 D02 I

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(d)(2)(i):The employer did not establish a LOTO program consisting of energy control procedures, employee training, and periodic inspections to ensure that, before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up, or release of stored energy could occur and cause injury, the machine or equipment is isolated from the energy source and rendered inoperative:  (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not establish a LOTO program consisting of energy control procedures, employee training, and periodic inspections, for servicing or maintenance of high voltage switchgear and associated equipment.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

1910.269 D02 III

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(d)(2)(iii): Procedures were not developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section:   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not have LOTO procedures developed or documented to perform racking-in/racking-out, or to shut down and deenergize the 4160-volt switchgear and breaker.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

1910.269 D02 VI

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(d)(2)(vi): The employer did not provide training to ensure that the purpose and function of the energy control program were understood by employees and that the knowledge and skills required for the safe application, usage, and removal of energy controls were acquired by employees:   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not provide LOTO training to ensure the knowledge and skills required for the safe application, usage, and removal of energy controls for job task including but not limited to racking circuit breakers in high voltage switchgear.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

1910.269 D02 VI A

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.269(d)(2)(vi)(A): Each authorized employee was not trained in the recognition of applicable hazardous energy sources, the type and magnitude of energy available in the workplace, and in the methods and means necessary for energy isolation and control:   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not provide authorized employees with training in recognition of hazardous energy sources, such as identification of energized equipment, and the methods and means for energy isolation and control, such as safe energy control procedures for racking circuit breakers in high voltage switchgear.
Recent events (2)
  • — C (S) $0
  • — Z (S) $0

1910.269 D03 I

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(d)(3)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware were not provided by the employer for isolating, securing, or blocking of machines or equipment from energy sources.   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not have LOTO hardware to safely secure and isolate the 4160-volt switchgear and breaker.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

1910.269 L01 II

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(l)(1)(ii): Where employees work on or near exposed live parts, the employer did not ensure that only qualified employees worked in areas containing unguarded, uninsulated energized lines or parts of equipment operating at 50 volts or more:   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not ensure that qualified employees performed servicing and maintenance on high voltage switchgear and associated equipment.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

1910.269 L08 I

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $6,452 · Current $6,452
29 CFR  1910.269(l)(8)(i): The employer did not assess the workplace to identify employees exposed to hazards from flames or from electric arcs:  (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not assess the workplace to identify employees exposed to hazards from flames or electric arcs such as employees racking in a circuit breaker on high voltage switchgear or working in switchgear with covers off.
Recent events (2)
  • — C (S) $6452
  • — Z (S) $6452

1910.269 L08 II

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $6,452 · Current $6,452
29 CFR  1910.269(l)(8)(ii): For each employee exposed to hazards from electric arcs, the employer did not make a reasonable estimate of the incident heat energy to which the employee could be exposed:   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The employer did not make a reasonable estimate of the incident heat energy to which the employee could be exposed, such as when racking breakers in high voltage switchgear.
Recent events (2)
  • — C (S) $6452
  • — Z (S) $6452

1910.269 L08 V

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 20, 2024
Abate by
Dec 3, 2024
Penalty
Initial $16,131 · Current $16,131
29 CFR  1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2:   (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees were conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing.  The employer failed to provide the employees with FR clothing, rubber insulating glove, heavy-duty work shoes, and head protection.
Recent events (2)
  • — C (S) $16131
  • — Z (S) $16131

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347494056.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.