TROY, NY —
OSHA Inspection: RELEVATE POWER LLC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of RELEVATE POWER LLC. in 510 CONGRESS ST, TROY, NY 12180 (NAICS 221111). OSHA activity number 347494239.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RELEVATE POWER LLC.
- Site address
- 510 CONGRESS ST
- City
- TROY
- State
- NY
- ZIP
- 12180
- Mailing
- 230 PARK AVE, NEW YORK, NY 10017
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221111
- Employees
- 1
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.37 E
- Issued
- Nov 20, 2024
- Abate by
- Dec 3, 2024
- Penalty
- Initial $11,292 · Current $0 Reduced
General-duty citation text
29 CFR 1910.37(e): Employer did not install and or maintain an operable employee alarm system that had a distinctive signal to warn employees of fire or other emergencies: (a) Mount Ida Hydro Station, Control room platform: The employer did not maintain the employee alarm system in operating condition in the event of an emergency in that the fire alarm system in the hydro dam had indicated faults and warning lights.
Recent events (3)
- — F (S) $0
- — C (S) $11292
- — Z (S) $11292
1910.157 E01
- Issued
- Nov 20, 2024
- Abate by
- Dec 3, 2024
- Penalty
- Initial $11,292 · Current $8,469 Reduced
General-duty citation text
29 CFR 1910.157(e)(1): The employer did not do inspection, maintenance and testing of all portable fire extinguishers in the workplace: (a) Mount Ida Hydro Station, Control room platform: On or about May 21, 2024, the employer did not maintain and test the Badger Model # B10HA CO2 fire extinguisher located on the control platform near the incident scene. The Badger Model # B10HA CO2 fire extinguisher service tag showed last service in 2008.
Recent events (3)
- — F (O) $8469
- — C (S) $11292
- — Z (S) $11292
1910.269 A03 I A
- Issued
- Nov 20, 2024
- Abate by
- Dec 3, 2024
- Penalty
- Initial $11,292 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(a)(3)(i)(A): The host employer did not ensure that each of its employees were instructed in the hazardous conditions relevant to the employee's work that the contract employer was aware of as a result of information communicated to the contract employer by the host employer under paragraph (a)(3)(i) of this section: (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, sub-contractor employees conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing experienced an arc flash when the breaker contacted an energized cell during racking-in. The host employer did not inform the subcontractor of the characteristics of the host employers installation, including but limited to the nominal voltages of lines and equipment and maximum switching transient voltages.
Recent events (3)
- — F (S) $0
- — C (S) $11292
- — Z (S) $11292
More inspections in this industry (NAICS 221111)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347494239.