OSHA Inspection: SULLIVAN & MERRITT CONSTRUCTORS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SULLIVAN & MERRITT CONSTRUCTORS, INC. in 1329 WATERVILLE ROAD, SKOWHEGAN, ME 04976 (NAICS 236210). OSHA activity number 347520272.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sullivan & Merritt Constructors, INC. — free Get an email when a new federal OSHA severe-injury report for Sullivan & Merritt Constructors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1329 WATERVILLE ROAD
City
SKOWHEGAN
State
ME
ZIP
04976
Mailing
91 FREEDOM PART, HERMON, ME 04401
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236210
Employees
20
Ownership type
A

4 citations on file for this inspection.

1926.21 B02

Other-than-serious Gravity 10 1 instance 1 exposed
Issued
Jul 5, 2024
Penalty
Initial $13,574 · Current $9,000 Reduced
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his/her environment to control or eliminate any hazards or other exposure to illness or injury:  ER17 MCC29-F2D - The employer did not adequately instruct or train an employee of the potential arc flash hazards related to installing ground lugs in the Cuttler Hammer motor carrier control unit (MCC), resulting in an arc flash explosion injuring an employee.
Recent events (2)
  • — I (O) $9000
  • — Z (S) $13574

1926.95 A

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Jul 5, 2024
Penalty
Initial $13,574 · Current $9,000 Reduced
29 CFR 1926.95(a): Personal protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, or maintained in a sanitary and reliable condition it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation, or physical contact.  ER17 MCC29-F2D -� The employer did not ensure employees used the appropriate personal protective equipment needed to protect them from arc flash injuries while installing a ground lug in a motor control center.
Recent events (2)
  • — I (O) $9000
  • — Z (S) $13574

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 5, 2024
Penalty
Initial $15,970 · Current $15,970
29 CFR�1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: ��  Control Room ER17, MCC29-F2D - An employee contacted an energized 480-volt bus bar while drilling a quarter-inch hole in a ground bar in the bottom compartment of an energized motor control center.
Recent events (2)
  • — I (S) $15970
  • — Z (S) $15970

1926.416 A03

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 5, 2024
Penalty
Initial $0 · Current $0
29 CFR�1926.416(a)(3): The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take.�  Control Room ER17, MCC29-F2D The employer failed to determine if employees could contact any energized circuits before assigning employees to install ground lugs in a live Cuttler Hammer MCC unit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Sullivan & Merritt Constructors, INC.'s full OSHA safety record →