MARIETTA, GA —
OSHA Inspection: VTI OF GEORGIA, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VTI OF GEORGIA, INC. in 1491 COBB INDUSTRIAL DR STE A, MARIETTA, GA 30066 (NAICS 337110). OSHA activity number 347533226.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VTI OF GEORGIA, INC.
- Site address
- 1491 COBB INDUSTRIAL DR STE A
- City
- MARIETTA
- State
- GA
- ZIP
- 30066
- Mailing
- 1491 COBB INDUSTRIAL DR STE A, MARIETTA, GA 30066
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 337110
- Employees
- 12
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.212 A01
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(1):One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a. Near Northwest Wall by "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to laceration hazards, in that the employer did not maintain effective guarding on a "Maxx Air" industrial drum fan where there was a 2-3/8 inch opening on the face of the fan guard 4 inches from the fan blade where employees operate saws for the production of countertops. b. Cap Area: On or about June 6, 2024, and at times prior, the employer exposed employees to laceration hazards, in that the employer did not maintain effective guarding on a "Patton" industrial pedestal fan where there was a 4-1/4 inch opening on the face of the fan guard where employees perform tasks for manufacturing countertops.
Recent events (1)
- — Z (O) $0
1910.303 B02
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a. Northwest of Production Area near "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to electric shock hazards, in that the employer did not ensure that an Underwriters Laboratories listed relocatable power tap was connected directly to a branch circuit receptacle. b. Northwest of Production Area near "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to electric shock hazards, in that the employer did not ensure that an Underwriters Laboratories listed relocatable power tap was not daisy chained with flexible extension cords. c. Northwest of Production Area near "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to electric shock hazards, in that the employer did not ensure that an Underwriters Laboratories listed relocatable power tap was not attached to table surfaces.
Recent events (1)
- — Z (O) $0
1910.304 G05
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a. Near Northwest Wall by "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to electric shock hazards, in that the employer did not provide a continuous path to ground for a "Maxx Air" industrial drum fan where the ground pin was missing from the plug while employees operate saws for the production of countertops.
Recent events (1)
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a. Production Area, near two "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to electrical shock hazards, in that the employer used an extension cord as a substitute for fixed wiring to provide power to cord and plug connected overhead lighting while employees operate saws for the production of countertops. b. Production Area northwest wall at "Midwest Automation" CS 5230: On or about June 6, 2024, and at times prior, the employer exposed employees to electrical shock hazards, in that the employer used an extension cord as a substitute for fixed wiring to provide power to cord and plug connected overhead lighting. c. Production Area at miter saws: On or about June 6, 2024, and at times prior, the employer exposed employees to electrical shock hazards, in that the employer used extension cords as a substitute for fixed wiring to provide power to cord and plug connected overhead lighting, a "Ryobi" model TS1346 chop saw and a "Maxx Air" industrial drum fan while employees operate saws for the production of countertops.
Recent events (1)
- — Z (O) $0
1910.305 G01 IV D
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were used where attached to building surfaces: a. Column at northeast end of Production Area: On or about June 6, 2024 and at times prior, the employer exposed employees to fire hazards, in that the employer attached flexible cords to building surfaces where the cords were used to supply power to cord and plug connected lighting where employees operate saws in the production of wood and laminate countertops.
Recent events (1)
- — Z (O) $0
1910.305 G02 III
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a. Production Area; adjacent to "Ryobi" miter saw: On or about June 6, 2024, and at times prior, the employer exposed employees to electrical shock hazards, in that strain relief was not provided on an extension cord used to provide electrical current from a relocatable power tap to a "Maxx Air" industrial drum fan while employees perform tasks associated with the production of wood and laminate countertops. b. Production Area; CAP Area: On or about June 6, 2024, and at times prior, the employer exposed employees to electrical shock hazards, in that strain relief was not provided on the cord of a "Dayton" pedestal fan connected to a double gang receptacle box used as pendant receptacle while employees perform tasks associated with the production of wood and laminate countertops.
Recent events (1)
- — Z (O) $0
1910.1200 F06 II
- Issued
- Nov 20, 2024
- Abate by
- Dec 19, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical: a. Cap Area: On or about June 6, 2024, and at times prior, the employer exposed employees to hazards associated with flammable chemicals, in that the employer did not ensure that pump cans containing "Wilsonart" 110 Adhesive Solvent were labeled for chemical content where employees use the chemical to clean surfaces in the production of wood and laminate countertops.
Recent events (1)
- — Z (O) $0
More inspections at VTI of Georgia, INC.
View VTI of Georgia, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 337110)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347533226.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.