HOUSTON, TX —
OSHA Inspection: TAS ENERGY INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TAS ENERGY INC. in 12218 ROBIN BLVD, HOUSTON, TX 77045 (NAICS 333992). OSHA activity number 347564791.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TAS ENERGY INC.
- Site address
- 12218 ROBIN BLVD
- City
- HOUSTON
- State
- TX
- ZIP
- 77045
- Mailing
- 12218 ROBIN BLVD, HOUSTON, TX 77045
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333992
- Employees
- 90
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.141 A03 II
- Issued
- Oct 30, 2024
- Abate by
- Nov 7, 2024
- Penalty
- Initial $6,913 · Current $0 Reduced
General-duty citation text
29 CFR 1910.141(a)(3)(ii): Floor(s) of workroom(s) were not maintained, so far as practical, in a dry condition: a) On or about June 20, 2024, in the pipe fabrication building, where accumulated water on the facility floor was not cleaned up.
Recent events (2)
- — I (S) $0
- — Z (S) $6913
1910.252 B02 III
- Issued
- Oct 30, 2024
- Abate by
- Jan 13, 2025
- Penalty
- Initial $11,524 · Current $3,173 Reduced
General-duty citation text
29 CFR 1910.252(b)(2)(iii): Workers and other persons adjacent to the welding area were not required to wear appropriate goggles to protect them from the rays when noncombustible or flameproof screens or shields were not used: a) On or about June 20, 2024, in the pipe fabrication building, employees were not protected from welding rays by screens or goggles when passing by welding stations and working in adjacent areas.
Recent events (2)
- — I (O) $3173
- — Z (S) $11524
1910.303 B02
- Issued
- Oct 30, 2024
- Abate by
- Jan 13, 2025
- Penalty
- Initial $11,524 · Current $11,524
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about June 20, 2024, throughout the facility's welding stations, where relocatable power taps and extension cords were daisy chained and used, contrary to the equipment's listing and labeling.
Recent events (2)
- — I (O) $11524
- — Z (S) $11524
1910.304 G05
- Issued
- Oct 30, 2024
- Abate by
- Jan 13, 2025
- Penalty
- Initial $16,131 · Current $0 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) On or about June 20, 2024, at a welding station in bay 1, where the grounding prongs on a relocatable power tap and extension cord was removed, interrupting the equipment's path to ground. b) On or about June 20, 2024, at a welding station in bay 2, where the grounding prong on a pedestal fan was removed, interrupting the equipment's path to ground.
Recent events (2)
- — I (O) $0
- — Z (S) $16131
1910.305 G01 IV A
- Issued
- Oct 30, 2024
- Abate by
- Jan 13, 2025
- Penalty
- Initial $11,524 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about June 20, 2024, throughout the pipe fabrication building, where extension cords were permanently used to supply power to relocatable power taps, power tools, lights, and fans.
Recent events (2)
- — I (O) $0
- — Z (S) $11524
1910.305 G01 IV D
- Issued
- Oct 30, 2024
- Abate by
- Jan 13, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: a) On or about June 4, 2024, in bay 2, where an extension cord used to supply power to a light was attached to the building's steel frame.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Oct 30, 2024
- Abate by
- Jan 13, 2025
- Penalty
- Initial $9,218 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) On or about June 20, 2024, in bay 1 welding station, where the strain relief on a flexible cord used to power equipment was damaged. b) On or about June 20, 2024, in bay 2 welding station, where the strain relief on flexible cords used to power tools and equipment were damaged or missing.
Recent events (2)
- — I (O) $0
- — Z (S) $9218
More inspections at TAS Energy INC.
View TAS Energy INC.'s full OSHA safety record →
More inspections in this industry (NAICS 333992)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347564791.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.