Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TAS ENERGY INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TAS ENERGY INC. in 12218 ROBIN BLVD, HOUSTON, TX 77045 (NAICS 333992). OSHA activity number 347564791.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch TAS Energy INC. — free Get an email when a new federal OSHA severe-injury report for TAS Energy INC. is published. One employer, no account, unsubscribe in one click.
Establishment
TAS ENERGY INC.
Site address
12218 ROBIN BLVD
City
HOUSTON
State
TX
ZIP
77045
Mailing
12218 ROBIN BLVD, HOUSTON, TX 77045
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333992
Employees
90
Ownership type
A

7 citations on file for this inspection.

1910.141 A03 II

Deleted Serious Gravity 1 1 instance 2 exposed
Issued
Oct 30, 2024
Abate by
Nov 7, 2024
Penalty
Initial $6,913 · Current $0 Reduced
29 CFR 1910.141(a)(3)(ii): Floor(s) of workroom(s) were not maintained, so far as practical, in a dry condition:  a) On or about June 20, 2024, in the pipe fabrication building, where accumulated water on the facility floor was not cleaned up.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6913

1910.252 B02 III

Other-than-serious Gravity 5 1 instance 20 exposed
Issued
Oct 30, 2024
Abate by
Jan 13, 2025
Penalty
Initial $11,524 · Current $3,173 Reduced
29 CFR 1910.252(b)(2)(iii): Workers and other persons adjacent to the welding area were not required to wear appropriate goggles to protect them from the rays when noncombustible or flameproof screens or shields were not used:  a) On or about June 20, 2024, in the pipe fabrication building, employees were not protected from welding rays by screens or goggles when passing by welding stations and working in adjacent areas.
Recent events (2)
  • — I (O) $3173
  • — Z (S) $11524

1910.303 B02

Other-than-serious Gravity 5 1 instance 20 exposed
Issued
Oct 30, 2024
Abate by
Jan 13, 2025
Penalty
Initial $11,524 · Current $11,524
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) On or about June 20, 2024, throughout the facility's welding stations, where relocatable power taps and extension cords were daisy chained and used, contrary to the equipment's listing and labeling.
Recent events (2)
  • — I (O) $11524
  • — Z (S) $11524

1910.304 G05

Other-than-serious Gravity 10 2 instances 20 exposed
Issued
Oct 30, 2024
Abate by
Jan 13, 2025
Penalty
Initial $16,131 · Current $0 Reduced
29 CFR  1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a) On or about June 20, 2024, at a welding station in bay 1, where the grounding prongs on a relocatable power tap and extension cord was removed, interrupting the equipment's path to ground.   b) On or about June 20, 2024, at a welding station in bay 2, where the grounding prong on a pedestal fan was removed, interrupting the equipment's path to ground.
Recent events (2)
  • — I (O) $0
  • — Z (S) $16131

1910.305 G01 IV A

Other-than-serious Gravity 5 1 instance 20 exposed
Issued
Oct 30, 2024
Abate by
Jan 13, 2025
Penalty
Initial $11,524 · Current $0 Reduced
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) On or about June 20, 2024, throughout the pipe fabrication building, where extension cords were permanently used to supply power to relocatable power taps, power tools, lights, and fans.
Recent events (2)
  • — I (O) $0
  • — Z (S) $11524

1910.305 G01 IV D

Other-than-serious Gravity 5 1 instance 20 exposed
Issued
Oct 30, 2024
Abate by
Jan 13, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:  a) On or about June 4, 2024, in bay 2, where an extension cord used to supply power to a light was attached to the building's steel frame.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 G02 III

Other-than-serious Gravity 5 2 instances 20 exposed
Issued
Oct 30, 2024
Abate by
Jan 13, 2025
Penalty
Initial $9,218 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a) On or about June 20, 2024, in bay 1 welding station, where the strain relief on a flexible cord used to power equipment was damaged.   b) On or about June 20, 2024, in bay 2 welding station, where the strain relief on flexible cords used to power tools and equipment were damaged or missing.
Recent events (2)
  • — I (O) $0
  • — Z (S) $9218

View TAS Energy INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347564791.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.