Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FEDERAL CORRECTIONAL INSTITUTION - PHOENIX

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FEDERAL CORRECTIONAL INSTITUTION - PHOENIX in 37900 N 45TH AVE, PHOENIX, AZ 85086 (NAICS 922140). OSHA activity number 347576019.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Federal Correctional Institution - Phoenix — free Get an email when a new federal OSHA severe-injury report for Federal Correctional Institution - Phoenix is published. One employer, no account, unsubscribe in one click.
Site address
37900 N 45TH AVE
City
PHOENIX
State
AZ
ZIP
85086
Mailing
37900 N 45TH AVE, PHOENIX, AZ 85086
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
200
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 18, 2024
Abate by
Jul 30, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2):Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.  VEHICLE MAINTENANCE: A drinking water fountain was not plugged into a ground fault circuit interrupter, exposing employees to electrical hazards.
Recent events (1)
  • — Z (S) $0

1910.305 A02 X

Serious Gravity 5 1 instance 5 exposed
Issued
Jul 18, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.305(a)(2)(x): Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.  FOOD WAREHOUSE: A flexible cord was routed through two doorways without protection from damage, exposing employees to electrical hazards
Recent events (1)
  • — Z (S) $0

1910.305 G01 III

Serious Gravity 5 2 instances 20 exposed
Issued
Jul 18, 2024
Abate by
Aug 13, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iii):If used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cord shall be equipped with an attachment plug and shall be energized from an approved receptacle outlet.  a) MAINTENANCE SHOPS: A 14AWG 3-conductor flexible cord, used as a tethered single receptacle, was wired permanently into a wall mounted junction box, exposing employees to fire and electrical hazards.   b) FRONT ENTRY GATE: A 14AWG 3-conductor flexible cord, used as a tethered single receptacle, was wired permanently into a wall mounted junction box, exposing employees to fire and electrical hazards.
Recent events (1)
  • — Z (S) $0