PHOENIX, AZ —
OSHA Inspection: FEDERAL CORRECTIONAL INSTITUTION - PHOENIX
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FEDERAL CORRECTIONAL INSTITUTION - PHOENIX in 37900 N 45TH AVE, PHOENIX, AZ 85086 (NAICS 922140). OSHA activity number 347576019.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FEDERAL CORRECTIONAL INSTITUTION - PHOENIX
- Site address
- 37900 N 45TH AVE
- City
- PHOENIX
- State
- AZ
- ZIP
- 85086
- Mailing
- 37900 N 45TH AVE, PHOENIX, AZ 85086
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 922140
- Employees
- 200
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Jul 18, 2024
- Abate by
- Jul 30, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2):Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. VEHICLE MAINTENANCE: A drinking water fountain was not plugged into a ground fault circuit interrupter, exposing employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 A02 X
- Issued
- Jul 18, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. FOOD WAREHOUSE: A flexible cord was routed through two doorways without protection from damage, exposing employees to electrical hazards
Recent events (1)
- — Z (S) $0
1910.305 G01 III
- Issued
- Jul 18, 2024
- Abate by
- Aug 13, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iii):If used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cord shall be equipped with an attachment plug and shall be energized from an approved receptacle outlet. a) MAINTENANCE SHOPS: A 14AWG 3-conductor flexible cord, used as a tethered single receptacle, was wired permanently into a wall mounted junction box, exposing employees to fire and electrical hazards. b) FRONT ENTRY GATE: A 14AWG 3-conductor flexible cord, used as a tethered single receptacle, was wired permanently into a wall mounted junction box, exposing employees to fire and electrical hazards.
Recent events (1)
- — Z (S) $0
More inspections at Federal Correctional Institution - Phoenix
View Federal Correctional Institution - Phoenix's full OSHA safety record →