OSHA Inspection: BUGLE ELECTRIC LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of BUGLE ELECTRIC LLC in DEEP BLUE OPERATING POE WELL #2 32.358343, -101.981937, TARZAN, TX 79783 (NAICS 213112). OSHA activity number 347592255.

Watch Bugle Electric LLC — free Get an email when a new federal OSHA severe-injury report for Bugle Electric LLC is published. One employer, no account, unsubscribe in one click.
Establishment
BUGLE ELECTRIC LLC
Site address
DEEP BLUE OPERATING POE WELL #2 32.358343, -101.981937
City
TARZAN
State
TX
ZIP
79783
Mailing
3129 BUCK RUN, SAN ANGELO, TX 76901
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
45
Ownership type
A

3 citations on file for this inspection.

1910.132 D02

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $11292.00 · Current $6500.00 Reduced
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification which included the requirements as outlined in 29 CFR 1910.132(d)(2):  On or about June 26, 2024, at Deep Blue Operating Poe Well #2 in Martin County, TX, the employer failed to provide a workplace hazard assessment for electrical prior to employees performed work on a 4160 volt disconnect.
Recent events (2)
  • — I (S) $6500
  • — Z (S) $11292

1910.332 B01

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $11292.00 · Current $6500.00 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:   On or about June 26, 2024, at Deep Blue Operating Poe Well #2 Martin County, Texas, the employer did not ensure employee(s) were provided with electrical safety-related work practices for the use of electrical test instrumentation to verify de-energized electrical components, as employees worked on the 4160 volt electrical box.
Recent events (2)
  • — I (O) $6500
  • — Z (S) $11292

1910.333 B02

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $9680.00 · Current $0.00 Reduced
29 CFR  1910.333(b)(2):While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2).  On or about June 26, 2024, at Deep Blue Operating Poe Well #2 in Martin County, TX, the employer did not ensure MCC building components, including the exterior electrical box, were lockout or tagged out prior to employees working on/ testing energized conductors or circuit parts and exposed them to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9680