Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DELEK US ENERGY, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DELEK US ENERGY, INC. in 1000 MCHENRY STREET, EL DORADO, AR 71730 (NAICS 324110). OSHA activity number 347596116.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Delek US Energy, INC. — free Get an email when a new federal OSHA severe-injury report for Delek US Energy, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1000 MCHENRY STREET
City
EL DORADO
State
AR
ZIP
71730
Mailing
7102 COMMERCE WAY, BRENTWOOD, TN 37024
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
324110
Employees
350
Ownership type
A

2 citations on file for this inspection.

1910.119 F01 I C

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 11, 2024
Abate by
Jun 30, 2025
Penalty
Initial $16,131 · Current $16,131
1910.119(f)(1)(i)(C)  Temporary operations;  (a ) On or about June 27, 2024, in the Platformer unit (#9) at the Lion Oil Refinery in El Dorado, AR, the employer did not develop and implement written operating procedures that provided clear instructions for the temporary operation of transferring the hot water/condensate from condensate wash tank (Metal drum #009-030), located in unit #9 to caustic wash drum (006-0059), located in unit #6. Workers were exposed to the hazard of thermal burns from the hot condensate/steam when performing this temporary operation. (b) On or about June 27, 2024, in the Platformer unit (#9) at the Lion Oil Refinery in El Dorado, AR, the employer did not identify, evaluate and control potential hazards with a written operating procedure for a temporary operation involving the condensate wash tank (Metal drum #009-030), pump (#009-2060) and its connected piping and valves. Workers were exposed to the hazard of thermal burns from the hot condensate/steam when performing this temporary operation.
Recent events (3)
  • — F (S) $16131
  • — C (S) $16131
  • — Z (S) $16131

1910.119 E03 I

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Dec 11, 2024
Abate by
Jan 30, 2025
Penalty
Initial $16,131 · Current $0 Reduced
29 CFR 1910.119 (e)(3)(i): The Process Hazard Analysis did not address the hazards of the process:  On or about June 27, 2024, in the Platformer unit (#9) at the Lion Oil Refinery in El Dorado, AR, workers were exposed to thermal burns from the hot condensate/steam, when the employer did not identify, evaluate and control the hazardous condition of condensate wash tank (Metal drum #009-030), pump (#009-2060) and its connected piping and valves.
Recent events (3)
  • — F (S) $0
  • — C (S) $16131
  • — Z (S) $16131

View Delek US Energy, INC.'s full OSHA safety record →