Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BULK FLUID SYSTEMS, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BULK FLUID SYSTEMS, LLC in W5905 STATE ROAD 33, HORICON, WI 53032 (NAICS 325612). OSHA activity number 347604308.

Watch Bulk Fluid Systems, LLC — free Get an email when a new federal OSHA severe-injury report for Bulk Fluid Systems, LLC is published. One employer, no account, unsubscribe in one click.
Site address
W5905 STATE ROAD 33
City
HORICON
State
WI
ZIP
53032
Mailing
W5905 STATE ROAD 33, HORICON, WI 53032
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325612
Employees
2
Ownership type
A

3 citations on file for this inspection.

1910.106 F01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $2939.00 · Current $2057.00 Reduced

Hazardous substances 1660

29 CFR  1910.106(f)(1)(i): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C). Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), were not stored in closed containers, or in storage tanks above ground outside of buildings, or underground in accordance with paragraph (b) of this section:  On or about July 15, 2024, and at times prior where storage tanks were used indoors to receive, blend, store, and distribute up to an approximate total of 2000 gallons of Premium Wash -25 (Methyl alcohol 37.5%, Cas # 67-56-1, category 3 flammable liquid) adjacent to general use electrical, potential ignition sources, and in absence of adequate tank venting exposing employees to potential fire hazards.
Recent events (2)
  • — I (S) $2057.3
  • — Z (S) $2939

1910.106 F05 II

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances 1660

29 CFR  1910.106(f)(5)(ii): All electrical equipment and wiring were not of a type specified by and installed in accordance with Subpart S of this part:  On or about July 15, 2024, and at times prior where storage tanks were used indoors to receive, blend, store, and distribute up to an approximate total of 2000 gallons of Premium Wash -25 (Methyl alcohol 37.5%, Cas # 67-56-1, category 3 flammable liquid) adjacent to general use electrical, potential ignition sources, and in absence of adequate tank venting exposing employees to potential fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 F06

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00

Hazardous substances 1660

29 CFR  1910.106(f)(6): Sources of ignition. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), shall not be handled, drawn, or dispensed where flammable vapors may reach a source of ignition. Smoking shall be prohibited except in designated localities. "No Smoking" signs shall be conspicuously posted where hazard from flammable liquid vapors is normally present.  On or about July 15, 2024, and at times prior where storage tanks were used indoors to receive, blend, store and distribute up to an approximate total of 2000 gallons of Premium Wash -25 (Methyl alcohol 37.5%, Cas # 67-56-1, category 3 flammable liquid) adjacent to general use electrical, potential ignition sources, and in absence of adequate tank venting exposing employees to potential fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347604308.