HORICON, WI —
OSHA Inspection: BULK FLUID SYSTEMS, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of BULK FLUID SYSTEMS, LLC in W5905 STATE ROAD 33, HORICON, WI 53032 (NAICS 325612). OSHA activity number 347604308.
Where did this inspection happen?
- Establishment
- BULK FLUID SYSTEMS, LLC
- Site address
- W5905 STATE ROAD 33
- City
- HORICON
- State
- WI
- ZIP
- 53032
- Mailing
- W5905 STATE ROAD 33, HORICON, WI 53032
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325612
- Employees
- 2
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.106 F01 I
- Issued
- Abate by
- Penalty
- Initial $2939.00 · Current $2057.00 Reduced
1660
General-duty citation text
29 CFR 1910.106(f)(1)(i): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C). Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), were not stored in closed containers, or in storage tanks above ground outside of buildings, or underground in accordance with paragraph (b) of this section: On or about July 15, 2024, and at times prior where storage tanks were used indoors to receive, blend, store, and distribute up to an approximate total of 2000 gallons of Premium Wash -25 (Methyl alcohol 37.5%, Cas # 67-56-1, category 3 flammable liquid) adjacent to general use electrical, potential ignition sources, and in absence of adequate tank venting exposing employees to potential fire hazards.
Recent events (2)
- — I (S) $2057.3
- — Z (S) $2939
1910.106 F05 II
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
1660
General-duty citation text
29 CFR 1910.106(f)(5)(ii): All electrical equipment and wiring were not of a type specified by and installed in accordance with Subpart S of this part: On or about July 15, 2024, and at times prior where storage tanks were used indoors to receive, blend, store, and distribute up to an approximate total of 2000 gallons of Premium Wash -25 (Methyl alcohol 37.5%, Cas # 67-56-1, category 3 flammable liquid) adjacent to general use electrical, potential ignition sources, and in absence of adequate tank venting exposing employees to potential fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.106 F06
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
1660
General-duty citation text
29 CFR 1910.106(f)(6): Sources of ignition. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C), shall not be handled, drawn, or dispensed where flammable vapors may reach a source of ignition. Smoking shall be prohibited except in designated localities. "No Smoking" signs shall be conspicuously posted where hazard from flammable liquid vapors is normally present. On or about July 15, 2024, and at times prior where storage tanks were used indoors to receive, blend, store and distribute up to an approximate total of 2000 gallons of Premium Wash -25 (Methyl alcohol 37.5%, Cas # 67-56-1, category 3 flammable liquid) adjacent to general use electrical, potential ignition sources, and in absence of adequate tank venting exposing employees to potential fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 325612)
SALEM, VA—2026-06-11
KIK (VIRGINIA) LLC
SALEM, VA—2026-06-11
KIK (VIRGINIA) LLC
SALEM, VA—2026-05-26
KIK (VIRGINIA) LLC
GARLAND, TX—2026-05-19
ZOBELE USA INC.
ZION, IL—2026-05-11
RITECHEM USA, LLC DBA PCL GLOBAL
More inspections in WI
WAUSAU, WI—2026-07-16
MIRON CONSTRUCTION CO. INC.
ELROY, WI—2026-07-15
WABASH NATIONAL SERVICES, L.P.
SUSSEX, WI—2026-07-15
KINGS SUPERIOR CONSTRUCTION LLC
DELAVAN, WI—2026-07-15
TERONOMY BUILDERS, INC.
DELAVAN, WI—2026-07-15
A. GOMEZ CARPENTRY, INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347604308.