Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: QUALITY INN NAVAJO NATION CAPITAL

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of QUALITY INN NAVAJO NATION CAPITAL in 48 ARIZONA 264, WINDOW ROCK, AZ 86515 (NAICS 721110). OSHA activity number 347627622.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Quality INN Navajo Nation Capital — free Get an email when a new federal OSHA severe-injury report for Quality INN Navajo Nation Capital is published. One employer, no account, unsubscribe in one click.
Site address
48 ARIZONA 264
City
WINDOW ROCK
State
AZ
ZIP
86515
Mailing
48 ARIZONA 264, WINDOW ROCK, AZ 86515
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
68
Ownership type
A

3 citations on file for this inspection.

1910.303 G01 I B

Serious Gravity 1 1 instance 5 exposed
Issued
Aug 29, 2024
Penalty
Initial $4,113 · Current $2,262 Reduced
29 CFR  1910.303(g)(1)(i)(B):For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater :  ELECTRICAL ROOM: On or about 07-17-2024 and times prior too, employees were exposed to electrical and fire hazards when materials were stored blocking electrical distribution panels and disconnects.
Recent events (2)
  • — I (S) $2262
  • — Z (S) $4113

1910.305 G01 IV B

Serious Gravity 5 3 instances 10 exposed
Issued
Aug 29, 2024
Abate by
Sep 11, 2024
Penalty
Initial $8,067 · Current $4,437 Reduced
29 CFR  1910.305(g)(1)(iv)(B):Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through holes in walls, ceilings, or floors.  A.) KITCHEN: On or about 07-17-2024 and times prior too, a flexible cord was run through the ceiling tiles and over a wall to power an reverse osmosis system exposing employees to fire dangers.  B.) LAUNDRY: On or about 07-17-2024 and times prior too, a flexible cord was run through the wall to power laundry equipment exposing employees to fire dangers.  C.) LOBBY EXIT: On or about 07-17-2024 and times prior too, a flexible cord was run through the aluminum door frame exposing employees to fire dangers.
Recent events (2)
  • — I (S) $4437
  • — Z (S) $8067

1910.101 B

Other-than-serious 1 instance 5 exposed
Issued
Aug 29, 2024
Abate by
Sep 11, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.101(b):The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  KITCHEN: On or about 07/17/24 and times prior too, employees were exposed to struck by hazards from unsecured compressed gas cylinders of carbon dioxide used for soft drinks.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Quality INN Navajo Nation Capital's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347627622.