EL DORADO, AR —
OSHA Inspection: AMERCABLE INCORPORATED
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of AMERCABLE INCORPORATED in 350 BAILEY RD., EL DORADO, AR 71730 (NAICS 335929). OSHA activity number 347644940.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMERCABLE INCORPORATED
- Site address
- 350 BAILEY RD.
- City
- EL DORADO
- State
- AR
- ZIP
- 71730
- Mailing
- 350 BAILEY RD., EL DORADO, AR 71730
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 335929
- Employees
- 278
- Ownership type
- A
Citations
6 citations on file for this inspection.
1904.39 A02
- Issued
- Jan 15, 2025
- Penalty
- Initial $9,795 · Current $4,897 Reduced
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye: On or about July 16, 2024, an employees sustained work-related injuries resulting in an amputation; the employer did not report the incident to OSHA within 24-hours.
Recent events (2)
- — I (O) $4897
- — Z (O) $9795
1910.28 B01 I
- Issued
- Jan 15, 2025
- Abate by
- Feb 7, 2025
- Penalty
- Initial $7,835 · Current $3,917 Reduced
General-duty citation text
29 CFR 1910.28(b)(1)(i): Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i): On or about July 24, 2024, on the A-Line by the coated wire accumulator, employees performing continuous vulcanizing activities used a platform at a height of 4-feet or greater from a lower level without fall protection in that: a) no guardrail was installed on the side facing the accumulator. b) no fall protection was provided at the ladder access to the platform.
Recent events (2)
- — I (O) $3917
- — Z (S) $7835
1910.147 C05 II
- Issued
- Jan 15, 2025
- Abate by
- Feb 7, 2025
- Penalty
- Initial $16,131 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(ii): Lockout devices and tagout devices were not used for lockout and tagout purposes only: On or about July 17, 2024, at electrical panel AL-13, a lock designated for lockout/tagout purposes was applied to an inactive breaker.
Recent events (2)
- — I (O) $1500
- — Z (S) $16131
1910.147 C05 II D
- Issued
- Jan 15, 2025
- Abate by
- Feb 7, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(5)(ii)(D): Lockout devices and tagout devices did not indicate the identity of the employee applying the device(s): On or about July 17, 2024, when locking out the electrical energy for electrical panel AL-13 the lockout device did not identify the employee utilizing the device.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Jan 15, 2025
- Abate by
- Feb 7, 2025
- Penalty
- Initial $16,131 · Current $8,065 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: On or about July 24, 2024, on the A-Line, employees were performing continuous vulcanizing where reel rolling tools obstructed electrical panel AL-13.
Recent events (2)
- — I (O) $8065
- — Z (S) $16131
1910.304 G05
- Issued
- Jan 15, 2025
- Penalty
- Initial $16,131 · Current $8,065 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about July 24, 2024, on the A-Line, employees were performing continuous vulcanizing, where the grounding prong was interrupting the equipment's path to ground in that: a) Two Profitter drum fans were missing ground pins. b) One Profitter drum fan was plugged into the outlet upside down.
Recent events (2)
- — I (O) $8065
- — Z (S) $16131
More inspections in this industry (NAICS 335929)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347644940.