CORPUS CHRISTI, TX —
OSHA Inspection: CITGO REFINING & CHEMICALS COMPANY LP
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CITGO REFINING & CHEMICALS COMPANY LP in 1802 NUECES BAY BLVD, CORPUS CHRISTI, TX 78407 (NAICS 324110). OSHA activity number 347645442.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CITGO REFINING & CHEMICALS COMPANY LP
- Site address
- 1802 NUECES BAY BLVD
- City
- CORPUS CHRISTI
- State
- TX
- ZIP
- 78407
- Mailing
- 1802 NUECES BAY BLVD, CORPUS CHRISTI, TX 78407
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 595
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 J02
- Issued
- Dec 3, 2024
- Abate by
- Jan 22, 2025
- Penalty
- Initial $16,131 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment: (a) On July 24, 2024, and at times prior, at the Citgo refinery facility (FCCU) in Corpus Christi, Texas, the employer did not develop an MI program procedure for calibrating the engineering controls that are intended to act as a safeguard for the gas compressor 032-C-001 including: I) 032-PSH-007 - Pressure Switch II) 32-TIT-003 - 2nd Stage Disc High Temp III) 032-TIT-124 - Lube Oil Supply High Temp (b) On July 24, 2024, and at times prior, at the Citgo refinery facility (FCCU) in Corpus Christi, Texas, the employer did not specify the inspection frequency requirements in its mechanical integrity program procedures for all control equipment that serves as safeguards for Gas Compressor 032-C-001, including the shutdown and alarm systems. (c) On July 24, 2024, and at times prior, at the Citgo refinery facility (FCCU) in Corpus Christi, Texas, the employer did not list inspection frequency requirements in its mechanical integrity program procedures for critical check valves.
Recent events (3)
- — R (S) $0
- — C (S) $16131
- — Z (S) $16131
1910.119 J04 I
- Issued
- Dec 3, 2024
- Abate by
- Jan 22, 2025
- Penalty
- Initial $16,131 · Current $16,131
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment: a) On July 24, 2024, and at times prior, at the Citgo refinery facility (FCCU) in Corpus Christi, Texas, the employer did not perform inspections on the 3" Critical Check Valve on the discharge of sponge oil pumps 032P007B - (P&ID 32-4-8113C). b) On July 24, 2024, and at times prior, at the Citgo refinery facility (FCCU) in Corpus Christi, Texas, the employer did not perform inspections and tests on the High-level switch 032LSH-001A (P&ID32-4-8110A REV#: 15).
Recent events (3)
- — R (O) $16131
- — C (S) $16131
- — Z (S) $16131
More inspections at Citgo Refining & Chemicals Company LP