Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: APOLLO METALS LTD,

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of APOLLO METALS LTD, in 1001 14TH AVENUE, BETHLEHEM, PA 18016 (NAICS 331410). OSHA activity number 347650145.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Apollo Metals LTD, — free Get an email when a new federal OSHA severe-injury report for Apollo Metals LTD, is published. One employer, no account, unsubscribe in one click.
Establishment
APOLLO METALS LTD,
Site address
1001 14TH AVENUE
City
BETHLEHEM
State
PA
ZIP
18016
Mailing
1001 14TH AVENUE, BETHLEHEM, PA 18016
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331410
Employees
60
Ownership type
A

2 citations on file for this inspection.

1910.151 C

Serious Gravity 1 1 instance 17 exposed
Issued
Jan 17, 2025
Penalty
Initial $3,724 · Current $3,724
29 CFR  1910.151(c): Where the employer provided employees with an emergency eyewash station, the eyewash station was not maintained in proper working condition:    (a) Production work area, Column W-2: On or about July 25, 2024, the eyewash station located adjacent to column W-2 was not maintained in proper working order in that the supplied water pressure was not maintained at a level to be non-injurious  to an employee user.  NOTE 1: Proper maintenance and weekly testing is necessary to ensure that Emergency Drench Showers and Eyewash Stations are functioning safely and properly. Weekly testing helps clear the supply lines of sediment and bacteria build-up that is caused from stagnant water. The ANSI standard states that plumbed flushing equipment, "shall be activated weekly for a period long enough to verify operation and ensure that flushing fluid is available".  Furthermore, the ANSI Z358.1-2009 standard also requires Portable and Self Contained equipment "be visually checked to determine if flushing fluid needs to be changed or supplemented". (ANSI Z358.1-2009)
Recent events (1)
  • — Z (S) $3724

1910.303 B07 I

Serious Gravity 1 1 instance 17 exposed
Issued
Jan 17, 2025
Penalty
Initial $3,724 · Current $3,724
29 CFR  1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.  (a) Production work area, Column W-2: On or about July 25, 2024, employees are exposed to an electric shock hazard due to a missing "knockout" on the Square D electrical disconnect/junction box located on column W-2.
Recent events (1)
  • — Z (S) $3724

View Apollo Metals LTD,'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347650145.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.