Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: KIOWA LINE BUILDERS INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of KIOWA LINE BUILDERS INC in GPS COORDINATES 36.9180412, -92.2488098, VANZANT, MO 65768 (NAICS 238990). OSHA activity number 347654014.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kiowa Line Builders INC for free Get an email when a new federal OSHA severe-injury report for Kiowa Line Builders INC is published. One employer, no account, unsubscribe in one click.
Site address
GPS COORDINATES 36.9180412, -92.2488098
City
VANZANT
State
MO
ZIP
65768
Mailing
801 MISSOURI HWY 5 SOUTH, TIPTON, MO 65081
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238990
Employees
200
Ownership type
Private (A)

3 citations on file for this inspection.

1926.600 A06 I

Other-than-serious Gravity 10 1 instance 5 exposed
Issued
Nov 8, 2024
Penalty
Initial $14,518 · Current $11,614 Reduced
29 CFR  1926.600(a)(6)(i):29 CFR 1926.600(a)(6)(i):  For lines rated 50kV or below, a minimum of 10 feet was not maintained between the energized line and the equipment.  At a worksite located near GPS Coordinates 36.9180412, -92.2488098, Vanzant, MO; employees were exposed to electric shock, electrocution, and fire hazards when replacing a transformer.  Employees working on a live 7,200-volt line with a derrick boom were not adequately protected from a minimum distance of 10 feet from the boom's claw to the energized line.  On 7-29-2024, an operator of the derrick made contact with the derrick's claw with the energized line, causing electricity to travel through the vehicle and shock an employee touching the vehicle, resulting in an in-patient hospitalization.
Recent events (2)
  • · I (O) $11614.4
  • · Z (S) $14518

1926.600 A06 IV

Other-than-serious Gravity 10 1 instance 5 exposed
Issued
Nov 8, 2024
Penalty
Initial $0 · Current $0
29 CFR  1926.600(a)(6)(iv):A person shall be designated to observe clearance of the equipment and give timely warning for all operations where it is difficult for the operator to maintain the desired clearance by visual means;  At a worksite located near GPS Coordinates 36.9180412, -92.2488098, Vanzant, MO; employees were exposed to electric shock, electrocution, and fire hazards when replacing a transformer. Employees working on a live 7,200-volt line with a derrick boom did not designate a specific employee to observe the clearance of equipment and give a timely warning for the operation. On 7-29-2024, an operator of the derrick made contact with the derrick's claw with the energized line, causing electricity to travel through the vehicle and shock an employee touching the vehicle, resulting in an in-patient hospitalization.
Recent events (2)
  • · I (O) $0
  • · Z (S) $0

1926.600 A06 VII A

Other-than-serious Gravity 10 1 instance 5 exposed
Issued
Nov 8, 2024
Penalty
Initial $14,518 · Current $11,614 Reduced
29 CFR  1926.600(a)(6)(vii)(A):The equipment shall be provided with an electrical ground directly to the upper rotating structure supporting the boom;   At a worksite located near GPS Coordinates 36.9180412, -92.2488098, Vanzant, MO; employees were exposed to electric shock, electrocution, and fire hazards when replacing a transformer. Employees working on a live 7,200-volt line with a derrick boom were not adequately protected from shock hazards when the equipment was not   adequately grounded. On 7-29-2024, an operator of the derrick made contact with the derrick's claw with the energized line, causing electricity to travel through the vehicle and shock an employee touching the vehicle, resulting in an in-patient hospitalization.
Recent events (2)
  • · I (O) $11614.4
  • · Z (S) $14518

View Kiowa Line Builders INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 347654014.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.