SEATTLE, WA —
OSHA Inspection: VETERANS HEALTH ADMINISTRATION, PUGET SOUND HEALTH CARE SYSTEM, SEATTLE CAMPUS, SEATTLE HOSPITAL
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VETERANS HEALTH ADMINISTRATION, PUGET SOUND HEALTH CARE SYSTEM, SEATTLE CAMPUS, SEATTLE HOSPITAL in 1660 S COLUMBIAN WAY BUILDING 100, SEATTLE, WA 98108 (NAICS 622110). OSHA activity number 347668238.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VETERANS HEALTH ADMINISTRATION, PUGET SOUND HEALTH CARE SYSTEM, SEATTLE CAMPUS, SEATTLE HOSPITAL
- Site address
- 1660 S COLUMBIAN WAY BUILDING 100
- City
- SEATTLE
- State
- WA
- ZIP
- 98108
- Mailing
- 1660 S COLUMBIAN WAY PSHS (S-00-SAFE), SEATTLE, WA 98108
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 4458
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.37 B02
- Issued
- Oct 18, 2024
- Abate by
- Nov 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) Pipe Shop, Mechanical Equipment Room #5 (Bldg. 100): On or about July 22nd, 2024 the designated emergency exit doors that opened into the exit access were not equipped with exit signage. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(2), which was contained in OSHA inspection number 1651105, citation no. 2, item no. 1, and was affirmed as a final order on May 23rd, 2023 with respect to a workplace at Vancouver, WA. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(2), which was contained in OSHA inspection number 1650384, citation no. 2, item no. 1, and was affirmed as a final order on May 23rd, 2023 with respect to a workplace at Vancouver, WA. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(2), which was contained in OSHA inspection number 1607692, citation no. 1, item no. 1, and was affirmed as a final order on September 1st, 2022 with respect to a workplace at Walla Walla, WA.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Oct 18, 2024
- Abate by
- Nov 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Energy Plant Engineering Shop, Break Room (Bldg. 100): On or about July 22nd, 2024 a Tripplite relocatable power tap (RPT) surge protector (Model No. TLP606 Series #AG-0015) was used to provide power to a Keurig Single Serve coffee maker and a Mr. Coffee coffee maker, exposing employees to electrical hazards. b) Pipe Shop (Bldg. 100): On or about July 22nd, 2024 three relocatable power tap (RPT) surge protectors were daisy chained and used to supply power to computers, monitors, charging docking stations, and printers, exposing employees to electrical hazards. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1706199 citation no. 1, item no. 1, and was affirmed as a final order on December 12th, 2023 with respect to a workplace at Spokane, WA.
Recent events (1)
- — Z (R) $0
1910.303 G01 II
- Issued
- Oct 18, 2024
- Abate by
- Nov 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) Pharmacy Out-Patient (Bldg. 100): On or about July 24nd, 2024, a control panel for a Omnicell ROBOT-Rx Central Pharmacy Robotic System was positioned and bolted in front of the facility's electrical panel, delaying emergency access, interfering with proper equipment operations, and compromising equipment inspections. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(1)(ii), which was contained in OSHA inspection number 1607692, citation no. 1, item no. 4 and was affirmed as a final order on September 1st, 2022 with respect to a workplace at Walla Walla, WA.
Recent events (1)
- — Z (R) $0
1910.305 G01 IV A
- Issued
- Oct 18, 2024
- Abate by
- Nov 14, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: a) Pharmacy Out-Patient (Bldg. 100): On or about July 24nd, 2024, in lieu of permanent wiring, an (12 gauge) orange-colored extension cord was used in order to provide power to a Thermo Scientific Refrigerator. Employees who use the refrigerator to storge sampling media were not protected from minor shock and/or potential electric hazards if the extension cord became compromised The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 1687933, citation no. 1, item no. 2, and was affirmed as a final order on September 20th, 2023 with respect to a workplace at Yakima Valley, WA. The U.S. Department of Veterans Affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 1650387, citation no. 1, item no. 3, and was affirmed as a final order on May 23rd, 2023 with respect to a workplace at Vancouver, WA.
Recent events (1)
- — Z (R) $0
More inspections at Veterans Health Administration, Puget Sound Health Care System, Seattle Campus, Seattle Hospital
More inspections in this industry (NAICS 622110)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347668238.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.