ALBANY, NY —
OSHA Inspection: KRUEGER ELECTRICAL CONTRACTING LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of KRUEGER ELECTRICAL CONTRACTING LLC in 1 CROSSGATES ROAD SUITE R203, ALBANY, NY 12203 (NAICS 238210). OSHA activity number 347680621.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KRUEGER ELECTRICAL CONTRACTING LLC
- Site address
- 1 CROSSGATES ROAD SUITE R203
- City
- ALBANY
- State
- NY
- ZIP
- 12203
- Mailing
- 519 QUEENSBURY AVENUE, QUEENSBURY, NY 12804
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 18
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.416 A01
- Issued
- Jan 23, 2025
- Abate by
- Jan 29, 2025
- Penalty
- Initial $5,675 · Current $4,256 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: a) Worksite, electrical room, switchgear: On or about July 29, 2024, an employee was pulling a circuit while standing on top of an electrical switchgear that was energized. The employee cut into a 120v single-phase wire and received an electric shock.
Recent events (2)
- — I (O) $4256.25
- — Z (S) $5675
1926.417 A
- Issued
- Jan 23, 2025
- Abate by
- Jan 29, 2025
- Penalty
- Initial $5,675 · Current $4,256 Reduced
General-duty citation text
29 CFR 1926.417(a): Controls that were to be deactivated during the course of work on energized or de-energized equipment or circuits were not tagged: a) Worksite, electrical room, switchgear: On or about July 29, 2024, an employee was pulling a circuit while standing on top of an electrical switchgear that was energized. The circuit was not tagged and the employee cut into a 120v single-phase wire, receiving an electric shock.
Recent events (2)
- — I (O) $4256.25
- — Z (S) $5675
1926.501 B01
- Issued
- Jan 23, 2025
- Abate by
- Jan 29, 2025
- Penalty
- Initial $6,620 · Current $4,965 Reduced
General-duty citation text
29 CFR 1926.501(b)(1): Each employee on a walking/working surface with an unprotected side or edge which was 6 feet (1.8 m) or more above a lower level was not protected from falling by the use of guardrail systems, safety net systems, or personal fall arrest systems. a) Worksite, electrical room, switchgear: On or about July 29, 2024, an employee was conducting electrical work while standing on an electrical switchgear, approximately 8 feet above the floor, and was not protected from falls in that there was no personal fall arrest system established, guardrails installed, or a safety net installed.
Recent events (2)
- — I (S) $4965
- — Z (S) $6620
1926.503 A01
- Issued
- Jan 23, 2025
- Abate by
- Feb 3, 2025
- Penalty
- Initial $6,620 · Current $0 Reduced
General-duty citation text
29 CFR 1926.503(a)(1): The employer did not provide a training program for each employee potentially exposed to fall hazards to enable each employee to recognize the hazards of falling and the procedures to be followed in order to minimize these hazards: a) Worksite, electrical room, switchgear: On or about July 29, 2024, an employee was conducting electrical work while standing on an electrical switchgear, approximately 8 feet above the floor, and was not provided training on fall hazards and how to minimize those hazards.
Recent events (2)
- — I (O) $0
- — Z (S) $6620
1904.39 A02
- Issued
- Jan 23, 2025
- Penalty
- Initial $4,729 · Current $2,837 Reduced
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye. a) Worksite, back of REI store, electrical room: On or about July 29, 2024, the employer failed to report a work-related incident resulting in in-person hospitalization to OSHA within 24 hours.