Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: SUMMIT MEDICAL COMPASSION CENTER, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of SUMMIT MEDICAL COMPASSION CENTER, INC. in 66 ILLINOIS AVENUE, WARWICK, RI 02888 (NAICS 325411). OSHA activity number 347714156.

Watch Summit Medical Compassion Center, INC. — free Get an email when a new federal OSHA severe-injury report for Summit Medical Compassion Center, INC. is published. One employer, no account, unsubscribe in one click.
Site address
66 ILLINOIS AVENUE
City
WARWICK
State
RI
ZIP
02888
Mailing
66 ILLINOIS AVENUE, WARWICK, RI 02888
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325411
Employees
39
Ownership type
A

5 citations on file for this inspection.

1910.36 B01

Serious Gravity 10 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $11585.00 · Current $8110.00 Reduced
29 CFR 1910.36(b)(1): At least two exit routes were not available in the workplace to permit prompt evacuation of employees and other building occupants during an emergency, except as allowed in paragraph (b)(3) of this section. The exit routes must be located as far away as practical from each other so that if one exit route is blocked by fire or smoke, employees can evacuate using the second exit route.  (a) Extraction Laboratory: On or about August 26, 2024, the employer did not provide two means of emergency egress in a high hazard, high occupancy work area to allow for the safe exiting of employees in the event of an emergency.
Recent events (2)
  • — I (S) $8109.5
  • — Z (S) $11585

1910.305 G01 IV A

Serious Gravity 5 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $8441.00 · Current $5909.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.   (a) Extraction Laboratory: On or about August 26, 2024, employees were exposed to the electrical hazard of a flexible extension cord used as a substitute for the fixed wiring of a structure: 1) Above the ceiling in the main room and used to supply power to a power strip powering various equipment on the lab bench.  2) In the extraction room and used to supply power to the Apeks controller unit.
Recent events (2)
  • — I (S) $5908.7
  • — Z (S) $8441

1910.305 G01 IV B

Serious Gravity 5 2 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors.  (a) Extraction Laboratory: On or about August 26, 2024, employees were exposed to the electrical hazard of a flexible extension cord that was run through a hole in the ceiling in the main room and used to supply power to a power strip energizing various equipment on the lab bench.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.132 D02

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification which included the requirements as outlined in 29 CFR 1910.132(d)(2).   (a) Extraction Laboratory: On or about August 26, 2024, the employer did not verify that the required workplace hazard assessment had been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, and the date(s) of the hazard assessment.  Abatement Note:   Once the PPE Hazard Assessment is completed you shall:   Certify that the hazard assessment has been performed through a written certification in accordance with 1910.132(d)(2), which includes:  1) Identification of the workplace evaluated, 2) The person certifying the evaluation,  3) The date the evaluation was conducted.  Guidance on conducting and documenting a PPE Hazard Assessment can be found on OSHA's website at:     https://www.osha.gov/personal-protective-equipment
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.307 B

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.307(b): Areas designated as hazardous (classified) locations under the Class and Zone system and areas designated under the Class and Division system established after August 13, 2007, were not properly documented.  (a) Extraction Laboratory: On or about August 26, 2024, the employer had not properly documented the locations, including the Extraction Laboratory area where flammable liquids including ethanol were used in the extraction process under the Class and Zone system.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View SUMMIT MEDICAL COMPASSION CENTER, INC.'s full OSHA safety record →