SURRY, ME —
OSHA Inspection: NEXAMP, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NEXAMP, INC. in 491 SURRY ROAD, SURRY, ME 04629 (NAICS 237130). OSHA activity number 347723629.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEXAMP, INC.
- Site address
- 491 SURRY ROAD
- City
- SURRY
- State
- ME
- ZIP
- 04629
- Mailing
- 101 SUMMER STREET SUITE 2, BOSTON, MA 02109
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237130
- Employees
- 472
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.269 D02 III
- Issued
- Nov 18, 2024
- Penalty
- Initial $5,288 · Current $5,288
General-duty citation text
29 CFR 1910.269(d)(2)(iii): Procedures were not developed, documented, and used for the control of potentially hazardous energy covered by paragraph (d) of this section: Jobsite - Employer did not develop an energy isolating procedure prior to shutting down the string transformer and switch gear on Equipment Pad 2.
Recent events (1)
- — Z (S) $5288
1910.269 D02 V
- Issued
- Nov 18, 2024
- Penalty
- Initial $5,288 · Current $5,288
General-duty citation text
29 CFR 1910.269(d)(2)(v): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the provisions of paragraph (d) of this section were being followed: Jobsite - The employer failed to complete an annual inspection of the energy control procedures required to isolate the solar equipment at the Surry Road field.
Recent events (1)
- — Z (S) $5288
1910.269 D06 IV
- Issued
- Nov 18, 2024
- Penalty
- Initial $8,816 · Current $8,816
General-duty citation text
29 CFR 1910.269(d)(6)(iv): Lockout or tagout devices shall be affixed to each energy-isolating device by authorized employees: Equipment Pad 2 - 25 string transformers and the main switch were not secured with locks prior to opening the electrical equipment and starting maintenance work.
Recent events (1)
- — Z (S) $8816
More inspections at Nexamp, INC.
View Nexamp, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 237130)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347723629.