ENDICOTT, NY —
OSHA Inspection: BAE SYSTEMS CONTROLS INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BAE SYSTEMS CONTROLS INC. in 1098 CLARK STREET, ENDICOTT, NY 13760 (NAICS 334419). OSHA activity number 347789133.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BAE SYSTEMS CONTROLS INC.
- Site address
- 1098 CLARK STREET
- City
- ENDICOTT
- State
- NY
- ZIP
- 13760
- Mailing
- 1098 CLARK STREET, ENDICOTT, NY 13760
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 334419
- Employees
- 1500
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.333 A01
- Issued
- Feb 7, 2025
- Penalty
- Initial $14,187 · Current $7,094 Reduced
General-duty citation text
29 CFR 1910.333(a)(1):The employer failed to ensure that live parts were deenergized before employees began to work on or near live parts. a) BAE Systems Inc., 1098 Clark Street, Endicott, NY 13760, EMI Laboratory. On or about 9/24/2024, the employer failed to ensure that live parts on a test bench that included LISN 1, were deenergized before an employee began work on or near a live part resulting in that employee receiving an electrical shock.
Recent events (3)
- — F (S) $7093.5
- — C (S) $14187
- — Z (S) $14187
1910.333 B02 IV B
- Issued
- Feb 7, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B):Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that circuit elements and equipment parts were deenergized: a) BAE Systems Inc., 1098 Clark Street, Endicott, NY 13760, EMI Laboratory. On or about 9/24/2024, a qualified person did not use test equipment to test and verify a test bench that included LISN 1, was de-energized prior to performing work. The test bench that included LISN 1 was energized and when an employee began working on or near a live part on LISN 1, the employee received an electrical shock from a live part.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Feb 7, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: a) BAE Systems Inc., 1098 Clark Street, Endicott, NY 13760, EMI Laboratory. On or about 9/24/2024, an employee was working on an energized test bench that included LISN 1, without electrical protective equipment such as, but not limited to, gloves, and the employee received an electrical shock from a live part.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
More inspections at BAE Systems Controls INC.
View BAE Systems Controls INC.'s full OSHA safety record →
More inspections in this industry (NAICS 334419)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347789133.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.