PENN HILLS, PA —
OSHA Inspection: TURNER DAIRY FARMS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TURNER DAIRY FARMS in 1049 JEFFERSON ROAD, PENN HILLS, PA 15235 (NAICS 311511). OSHA activity number 347808081.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TURNER DAIRY FARMS
- Site address
- 1049 JEFFERSON ROAD
- City
- PENN HILLS
- State
- PA
- ZIP
- 15235
- Mailing
- 1049 JEFFERSON ROAD, PITTSBURGH, PA 15235
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311511
- Employees
- 215
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 E01 II
- Issued
- Dec 4, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Other markings giving voltage, current, wattage, or other ratings as necessary. a.) Jobsite, Tractor Trailer Staging Area, 1049 Jefferson Road, Pittsburgh, PA 15235: Observed, On or about October 10, 2024, electric high voltage receptacle(s) 3 phase (230v) and (4600v) watts tractor trailer refrigeration receptacle was damaged from burn markings on the receptacle. The receptacle was used to refrigerate product staged inside the trailer while parked.
Recent events (1)
- — Z (O) $0
1910.305 E01
- Issued
- Dec 4, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures. Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures and shall be mounted so there is at least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or other supporting surface. However, nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface. The enclosures shall be weatherproof in wet locations. a.) Observed, Tractor Trailer Staging Area, On or about October 10, 2024, the main electrical circuit panel breaker box had a damaged and bent cover that would not securely close, exposing employees to potential shock hazards.
Recent events (1)
- — Z (O) $0
More inspections at Turner Dairy Farms
View Turner Dairy Farms's full OSHA safety record →
More inspections in this industry (NAICS 311511)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347808081.