SAN DIEGO, CA —
OSHA Inspection: NAVY GATEWAY INN - AMPHIBIOUS BASE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NAVY GATEWAY INN - AMPHIBIOUS BASE in 3628 TULAGI ROAD, BLDG. 504, SAN DIEGO, CA 92155 (NAICS 721110). OSHA activity number 347825887.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAVY GATEWAY INN - AMPHIBIOUS BASE
- Site address
- 3628 TULAGI ROAD, BLDG. 504
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92155
- Mailing
- 3628 TULAGI ROAD, SAN DIEGO, CA 92155
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 11
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.22 D01
- Issued
- Nov 22, 2024
- Abate by
- Dec 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): The employer did not ensure that walking-working surfaces are inspected, regularly and as necessary, and maintained in a safe condition. Electrical room, Bldg. 504: On or about October 18th, 2024, and at times prior thereto, employee(s) engaged in technical activities. The employer did not ensure walking-working surfaces were maintained in a safe condition. Multiple boxes were stacked on top of the other in close proximity to the electrical. This condition potentially exposed employee(s) to fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.37 B01
- Issued
- Nov 22, 2024
- Abate by
- Dec 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(1): Each exit route was not adequately lighted so that employees with normal vision could see along the exit route. Employee Breakroom, Bldg. 504: On or about October 18th, 2024, and at times prior thereto, the employer did not ensure that the two sided-lights on the exit sign were operable. This condition potentially exposed employee(s) to fire hazard(s).
Recent events (1)
- — Z (S) $0
1910.38 C02
- Issued
- Nov 22, 2024
- Abate by
- Dec 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.38(c)(2): Procedures for emergency evacuation, including type of evacuation and exit route assignments were not implemented by the employer. Electrical Room near front desk, Bldg. 504: On or about October 18th, 2024, and at times prior thereto, employee(s) engaged in technical operation(s). The employer's Emergency Action plan did not include a review to show employee(s) where and/or how to evacuate in the event of an emergency specifically for, controlled access space(s). Employee(s) were potentially exposed to fire hazard(s) and/or egress hazard(s).
Recent events (1)
- — Z (S) $0
1910.38 C04
- Issued
- Nov 22, 2024
- Abate by
- Dec 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.38(c)(4): The emergency action plan, at a minimum, did not include procedure for accountability for all employees after evacuation. Electrical Room near front desk, Bldg. 504: On or about October 18th, 2024, and at times prior thereto, employee(s) engaged in technical operation(s). The employer did not include accountability procedures in the Emergency Action Plan to show employee(s) where to evacuate in the event of an emergency specifically for, controlled space(s). This condition potentially exposed employee(s) to fire hazard(s) and/or egress hazard(s).
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Nov 22, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. Housekeeping, Lead Office, Bldg. 504: On or about October 18th, 2024, and at times prior thereto, multiple appliances such as the Lasko Oscillating Ceramic Heater, ABSCOLD Compact Refrigerator, MicroFridge Microwave and a Bella 4 Slice Toaster were plugged into a relocatable power tap in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical and/or fire hazard(s). In the following locations: a) Housekeeping, Lead Office, Bldg. 504 - Lasko Oscillating Ceramic Heater and ABSCOLD Compact Refrigerator. b) Employee Breakroom, Bldg. 504 - MicroFridge Microwave and Bella 4 Slice Toaster
Recent events (1)
- — Z (S) $0
1910.303 G01 II
- Issued
- Nov 22, 2024
- Abate by
- Dec 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage. On or about October 18th, 2024, and at times prior thereto, the employer did not ensure at least 3 feet in front of the electrical panel was clear. The circuit breaker panel had multiple equipment such as a yellow mop bucket, cleaning supplies and a wooden table obstructing the panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s). In the following location(s): a) Electrical room, Bldg. 504 - Yellow mop bucket and cleaning supplies. b) Boiler room, Bldg. 504 - Wooden table
Recent events (1)
- — Z (S) $0
More inspections at Navy Gateway INN - Amphibious Base
View Navy Gateway INN - Amphibious Base's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347825887.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.