OSHA Inspection: NAVFACSYSCOM

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NAVFACSYSCOM in 1968 GILBERT ST. BUILDING W-143, NORFOLK, VA 23511 (NAICS 561210). OSHA activity number 347844888.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Navfacsyscom — free Get an email when a new federal OSHA severe-injury report for Navfacsyscom is published. One employer, no account, unsubscribe in one click.
Establishment
NAVFACSYSCOM
Site address
1968 GILBERT ST. BUILDING W-143
City
NORFOLK
State
VA
ZIP
23511
Mailing
9742 MARYLAND AVENUE, NORFOLK, VA 23511
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
2
Ownership type
D

2 citations on file for this inspection.

1910.333 B02 IV B

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 12, 2025
Abate by
Apr 7, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(iv)(B): A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage back feed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately after this test:   A) Norfolk Naval Base, 1968 Gilbert St. Building W-143 Norfolk VA 23511 on 10/19/ 2024: Employees worked replacing drive rods in Air Switch Vault 1A and 2A.  Energy control testing procedures were performed, but it failed to properly verify that circuit elements and equipment parts were deenergized.  Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (1)
  • — Z (S) $0

1960.8 A

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 12, 2025
Abate by
Apr 7, 2025
Penalty
Initial $0 · Current $0
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm in that employees were exposed to electrical shock hazards while working on an electrical switch, where the circuities, that deenergize the equipment, were not staying in the open position allowing for the potential of reenergization.  a)  Norfolk Naval Base, 1968 Gilbert St. Building W-143 Norfolk VA 23511: On or about 10/19/2024, the agency failed to perform  annual visual inspections and merger readings of the metal-enclosed switchgear as specified by the manufacturer, resulting in a drive rod failing to stay in the open position, thus causing third-degree burns to an employee.  Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (1)
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347844888.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.