Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMENTUM SERVICES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AMENTUM SERVICES, INC. in WORK CENTER 310 LINE SHACK, OAK HARBOR, WA 98277 (NAICS 488190). OSHA activity number 347846610.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Amentum Services, INC. — free Get an email when a new federal OSHA severe-injury report for Amentum Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
WORK CENTER 310 LINE SHACK
City
OAK HARBOR
State
WA
ZIP
98277
Mailing
1120 WEST ENTERPRISE RD. BLDG 2563, OAK HARBOR, WA 98277
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
71
Ownership type
A

6 citations on file for this inspection.

1910.36 B01

Other-than-serious Gravity 5 1 instance 71 exposed
Issued
Nov 21, 2024
Abate by
Dec 18, 2024
Penalty
Initial $7,835 · Current $7,835
29 CFR 1910.36(b)(1): At least two exits routes were not available to permit prompt evacuation of employees during an emergency:  a) Work Center 310 Line Shack: On or about October 25, 2024, where the workspace contained one exit route that led to one exit discharge door located at the front of the building. Hazard: Entrapment.
Recent events (2)
  • — I (O) $7835
  • — Z (S) $7835

1910.37 B02

Other-than-serious Gravity 5 1 instance 71 exposed
Issued
Nov 21, 2024
Abate by
Dec 18, 2024
Penalty
Initial $7,835 · Current $7,835
29 CFR  1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a) Work Center 310 Line Shack: On or about October 25, 2024, employees were exposed to workplace hazards because the emergency discharge door was not equipped with an exit sign.
Recent events (2)
  • — I (O) $7835
  • — Z (S) $7835

1910.37 B05

Other-than-serious Gravity 5 2 instances 71 exposed
Issued
Nov 21, 2024
Abate by
Dec 18, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  a) Work Center 310 Line Shack: On or about October 25, 2024, employees were exposed to safety hazards because doors located in along an exit access were not equipped with signage  indicating its actual use including:  1. Door to the office located adjacent to the Shift Lead desk.  2. Door that opened into the adjoining workspace occupied by military personnel.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 B02

Deleted Serious Gravity 5 3 instances 71 exposed
Issued
Nov 21, 2024
Penalty
Initial $9,795 · Current $0 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Work Center 310 Line Shack: On or about October 25, 2024, employees were exposed to electrical hazards where electrical equipment not used as listed or labeled included: 1. Appliance Area, where a relocatable power tap was attached to the back of the metal shelving with a zip-tie and daisy chained with the orange extension cord located on the floor behind the refrigerators and used to supply power to the flashlight battery chargers.   2. Appliance Area, where a relocatable power tap was daisy chained with the orange extension cord located on the floor behind the refrigerators and with the green extension cord and used to supply power to the GE microwave oven.  3. Appliance Area, where a relocatable power tap was daisy chained with the orange extension cord located on the floor behind the refrigerators and used to supply power to the Frigidaire refrigerator.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9795

1910.305 G01 IV A

Deleted Serious Gravity 5 1 instance 71 exposed
Issued
Nov 21, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Work Center 310 Line Shack: On or about October 25, 2024, where the orange extension cord located on the floor behind the refrigerators was used to supply power to two relocatable power taps and the beige refrigerator.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 E02

Deleted Other-than-serious 1 instance 71 exposed
Issued
Nov 21, 2024
Abate by
Dec 18, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  a) Work Center 310 Line Shack: On or about October 25, 2024, where employees would not be expected to fight incipient stage fires within the building, the Amerex 322 fire extinguisher was equipped with a monthly inspection tag dated June 2024.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Amentum Services, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347846610.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.