Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BP, INC., DBA BONOLLO PROVISIONS CO., INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BP, INC., DBA BONOLLO PROVISIONS CO., INC. in 55 CLARKSON STREET, PROVIDENCE, RI 02908 (NAICS 424410). OSHA activity number 347872434.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch BP, INC., DBA Bonollo Provisions CO., INC. — free Get an email when a new federal OSHA severe-injury report for BP, INC., DBA Bonollo Provisions CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
55 CLARKSON STREET
City
PROVIDENCE
State
RI
ZIP
02908
Mailing
55 CLARKSON STREET, PROVIDENCE, RI 02908
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424410
Employees
70
Ownership type
A

4 citations on file for this inspection.

1910.106 B06

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 7, 2025
Abate by
Apr 22, 2025
Penalty
Initial $11,585 · Current $5,793 Reduced
29 CFR 1910.106(b)(6): In locations where, flammable vapors may be present, precautions were not taken to prevent ignition by eliminating or controlling sources of ignition.  Sources of ignition may include open flames, lightning, smoking, hot surfaces, frictional heat, sparks (static, electrical, and mechanical), spontaneous ignition, chemical and physical-chemical reactions, and radiant heat.  a. Electrical room on the northeast side of the building: On or about 11/12/2024, the employer stored multiple cylinders of liquid propane gas that gave off an odor identifying potential leaking in the electrical room with an open unguarded circuit breaker panel.
Recent events (2)
  • — I (S) $5792.5
  • — Z (S) $11585

1910.303 G02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 7, 2025
Abate by
Apr 22, 2025
Penalty
Initial $8,276 · Current $4,138 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i).    a. Electrical room: On or about 12/26/2024, employees were exposed to electrical hazards while working with or near a live unguarded circuit breaker panel.
Recent events (2)
  • — I (S) $4138
  • — Z (S) $8276

1910.37 B02

Other-than-serious 1 instance 10 exposed
Issued
Mar 7, 2025
Abate by
Apr 22, 2025
Penalty
Initial $930 · Current $465 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit".   a. Dry storage area: On or about 11/12/2024, the doorway in the dry storage room was not clearly marked with a sign reading "Exit."
Recent events (2)
  • — I (O) $465
  • — Z (O) $930

1910.37 B05

Other-than-serious 1 instance 15 exposed
Issued
Mar 7, 2025
Abate by
Apr 22, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation or be identified by a sign indicating its actual use (e.g. closet).  a. Walk-in freezer: On or about 11/12/24, the doorway into the walk-in freezer was not identified as "Not an Exit" or similar designation and was not identified by a sign indicating its actual use.  b. On or about 11/12/24, the doorway into the refrigerated section was not identified as "Not an Exit."
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347872434.