Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EAGLE AVIATION SERVICES AND TECHNOLOGY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of EAGLE AVIATION SERVICES AND TECHNOLOGY in 708 MEYER DR, BLDG 2405, MARCH AIR RESERVE BASE, CA 92518 (NAICS 561210). OSHA activity number 347887960.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Eagle Aviation Services and Technology — free Get an email when a new federal OSHA severe-injury report for Eagle Aviation Services and Technology is published. One employer, no account, unsubscribe in one click.
Site address
708 MEYER DR, BLDG 2405
City
MARCH AIR RESERVE BASE
State
CA
ZIP
92518
Mailing
7450 HERITAGE VILLAGE PLAZA SUITE 202, GAINESVILLE, VA 20155
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
30
Ownership type
A

3 citations on file for this inspection.

1910.333 B02 II B

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Jan 7, 2025
Abate by
Jan 27, 2025
Penalty
Initial $8,067 · Current $0 Reduced
29 CFR  1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.  Bldg. 2404: On November 8th, 2024, and at times prior thereto, employee(s) were tasked to perform corrective maintenance work on an automatic transfer switch (ATS) unit whose energy source  was not disconnected from circuits and/or equipment. Also, the automatic transfer switch (ATS) unit had not been locked and/or tagged out properly during servicing and maintenance activities. This condition exposed employee(s) to arc flash hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $8067

1910.335 A01 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Jan 7, 2025
Abate by
Jan 17, 2025
Penalty
Initial $8,067 · Current $0 Reduced
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed.  Bldg. 2404: On November 8th, 2024, and at times prior thereto, employee(s) were tasked to perform corrective maintenance work on specific work order(s) for the day such as; electrical, plumbing, Heating, Ventilation, and Air Conditioning (HVAC) and painting. An employee was hospitalized due to severe charring, blistering, and damage to both front sides of the arms, hands and face from an Arc-Flash, due to, not using appropriate electrical protective equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $8067

1904.39 A02

Other-than-serious 1 instance 1 exposed
Issued
Jan 7, 2025
Abate by
Jan 17, 2025
Penalty
Initial $8,067 · Current $8,067
29 CFR  1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye.  Bldg. 2404: On November 8th, 2024, and at times prior thereto, employee(s) were tasked to perform corrective maintenance work on specific work order(s) for the day such as electrical, plumbing, Heating, Ventilation, and Air Conditioning (HVAC) and painting. An employee was hospitalized due to severe charring, blistering, and damage to both front sides of the arms, hands and face from an Arc-Flash that occurred from the Automatic Transfer Switch (ATS) Unit. A late notification to OSHA was made on November 14, 2024.
Recent events (2)
  • — I (O) $8067
  • — Z (O) $8067

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347887960.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.