MARCH AIR RESERVE BASE, CA —
OSHA Inspection: EAGLE AVIATION SERVICES AND TECHNOLOGY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of EAGLE AVIATION SERVICES AND TECHNOLOGY in 708 MEYER DR, BLDG 2405, MARCH AIR RESERVE BASE, CA 92518 (NAICS 561210). OSHA activity number 347887960.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EAGLE AVIATION SERVICES AND TECHNOLOGY
- Site address
- 708 MEYER DR, BLDG 2405
- City
- MARCH AIR RESERVE BASE
- State
- CA
- ZIP
- 92518
- Mailing
- 7450 HERITAGE VILLAGE PLAZA SUITE 202, GAINESVILLE, VA 20155
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 30
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.333 B02 II B
- Issued
- Jan 7, 2025
- Abate by
- Jan 27, 2025
- Penalty
- Initial $8,067 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures. Bldg. 2404: On November 8th, 2024, and at times prior thereto, employee(s) were tasked to perform corrective maintenance work on an automatic transfer switch (ATS) unit whose energy source was not disconnected from circuits and/or equipment. Also, the automatic transfer switch (ATS) unit had not been locked and/or tagged out properly during servicing and maintenance activities. This condition exposed employee(s) to arc flash hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $8067
1910.335 A01 I
- Issued
- Jan 7, 2025
- Abate by
- Jan 17, 2025
- Penalty
- Initial $8,067 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed. Bldg. 2404: On November 8th, 2024, and at times prior thereto, employee(s) were tasked to perform corrective maintenance work on specific work order(s) for the day such as; electrical, plumbing, Heating, Ventilation, and Air Conditioning (HVAC) and painting. An employee was hospitalized due to severe charring, blistering, and damage to both front sides of the arms, hands and face from an Arc-Flash, due to, not using appropriate electrical protective equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $8067
1904.39 A02
- Issued
- Jan 7, 2025
- Abate by
- Jan 17, 2025
- Penalty
- Initial $8,067 · Current $8,067
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye. Bldg. 2404: On November 8th, 2024, and at times prior thereto, employee(s) were tasked to perform corrective maintenance work on specific work order(s) for the day such as electrical, plumbing, Heating, Ventilation, and Air Conditioning (HVAC) and painting. An employee was hospitalized due to severe charring, blistering, and damage to both front sides of the arms, hands and face from an Arc-Flash that occurred from the Automatic Transfer Switch (ATS) Unit. A late notification to OSHA was made on November 14, 2024.
Recent events (2)
- — I (O) $8067
- — Z (O) $8067
More inspections in this industry (NAICS 561210)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347887960.