WAUKESHA, WI —
OSHA Inspection: PROLEC-GE WAUKESHA, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of PROLEC-GE WAUKESHA, INC. in 400 SOUTH PRAIRIE AVENUE, WAUKESHA, WI 53186 (NAICS 423850). OSHA activity number 347921660.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PROLEC-GE WAUKESHA, INC.
- Site address
- 400 SOUTH PRAIRIE AVENUE
- City
- WAUKESHA
- State
- WI
- ZIP
- 53186
- Mailing
- 400 SOUTH PRAIRIE AVENUE, WAUKESHA, WI 53186
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423850
- Employees
- 750
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.28 B01 I
- Issued
- May 16, 2025
- Abate by
- Jun 20, 2025
- Penalty
- Initial $10,050 · Current $10,050
General-duty citation text
29 CFR 1910.28(b)(1)(i):Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i): (a) On or about January 30, 2025, and dates prior, in the transformer "Sound Room" test area and other test areas, employees did not use fall protection while performing "Heat Run" tests, exposing employees to a fall hazard of up to 15 feet, when walking and working on the top of the transformer as part of the "Heat Run" test job task.
Recent events (2)
- — I (O) $10050
- — Z (S) $10050
1910.333 B02 IV A
- Issued
- May 16, 2025
- Abate by
- Jun 20, 2025
- Penalty
- Initial $16,550 · Current $16,550
General-duty citation text
1910.333(b)(2)(iv)(A) Before circuits or equipment were worked as deenergized, a qualified person did not operate the equipment operating controls or otherwise verify that the equipment could not be restarted:(a) (LOCATION) (IDENTIFY SPECIFIC OPERATIONS AND/OR CONDITIONS) 1910.333(b)(2)(iv)(A): A qualified person shall operate the equipment operating controls or otherwise verify that the equipment cannot be restarted. (a) On or about December 7, 2024, and days prior at the generator/ transformer and the lines used to transmit electrical energy from the generator to equipment in the "Sound Room" test area, the employer did not verify the main aisle switch was deenergized and in the open position to render the circuit inoperable. This exposed employees to electrical hazards.
Recent events (2)
- — I (S) $16550
- — Z (S) $16550
1910.333 B02 IV B
- Issued
- May 16, 2025
- Abate by
- Jun 20, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.333(b)(2)(iv)(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately after this test. 29 CFR 1910.269(m)(3)(vi): After the applicable requirements in paragraphs (m)(3)(i) through (m)(3)(v) of this section have been followed and the system operator gives a clearance to the employee in charge, the employer shall ensure that the lines and equipment are deenergized by testing the lines and equipment to be worked with a device designed to detect voltage. (a) On or about December 7, 2024, and days prior, at the generator/ transformer and the lines used to transmit electrical energy from the generator to equipment in the "Sound Room" test area, the employer did not require and ensure verification of de-energization of the circuit by testing the circuit with electrical test equipment. This exposed employees to electrical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 A01
- Issued
- May 16, 2025
- Abate by
- Jun 20, 2025
- Penalty
- Initial $10,050 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts that the employee was exposed to were not de-energized before the work began in or near them. (a) On or about December 7, 2024, and dates prior in the "Sound Room" test area, employees engaged in activities that included working inside the open and energized 110/208 single phase control panel for the transformer being tested, were exposed to electrical shock hazards when the panel was not de-energized and locked-out prior to work being conducted on the control panel.
Recent events (2)
- — I (S) $0
- — Z (S) $10050
1910.305 A02 X
- Issued
- May 16, 2025
- Abate by
- Jul 30, 2025
- Penalty
- Initial $10,050 · Current $10,050
General-duty citation text
1910.305(a)(2)(x) Flexible cords and cables shall be protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. 1910.333(b)(2)(iv)(B): A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately after this test. (a) On or about December 7, 2024, and dates prior in the "Sound Room" test area, employees were exposed to electrical shock hazard, and trip and fall hazard when the temporary cable wiring feeding the transformer control panel and unit ground wires were laid on the floor work area and not sufficiently protected against damage, accidental interruptions, and other hazards prior to work being conducted on and around the open 110/208 volt single phase control panel.
Recent events (2)
- — I (S) $10050
- — Z (S) $10050
1910.335 B03
- Issued
- May 16, 2025
- Abate by
- Jun 12, 2025
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(b)(3): Attendants. When signs and barricades did not provide sufficient warning and protection from electrical hazards, the employer did not station an attendant to warn and protect employees. (a) On or about December 7, 2024, and dates prior, at the entry door to the "Sound Room" test area and inside the "Sound Room", the stack light warning system (sign) used to alert Test Technicians of electrical hazards while working in the "Sound Room" was not working to alert exposed employees to the energized electrical circuit present in the "Sound Room". The employer did not assign and station an attendant to warn and protect employees from the energized electrical equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $16550
More inspections at Prolec-Ge Waukesha, INC.
View Prolec-Ge Waukesha, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423850)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347921660.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.