OSHA Inspection: ACTON TECHNOLOGIES, INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ACTON TECHNOLOGIES, INC in 100 THOMPSON STREET, PITTSTON, PA 18640 (NAICS 326199). OSHA activity number 347923393.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Acton Technologies, INC — free Get an email when a new federal OSHA severe-injury report for Acton Technologies, INC is published. One employer, no account, unsubscribe in one click.
Site address
100 THOMPSON STREET
City
PITTSTON
State
PA
ZIP
18640
Mailing
100 THOMPSON STREET, PITTSTON, PA 18640
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
326199
Employees
60
Ownership type
A

6 citations on file for this inspection.

1910.106 D05 V

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 14, 2025
Abate by
Mar 28, 2025
Penalty
Initial $8,276 · Current $5,200 Reduced
29 CFR 1910.106(d)(5)(v): Storage was not in accordance with Table H-14 or H-15 and in buildings or in portions of such buildings cut off by standard firewalls.  Material creating a fire exposure hazard to the flammable liquids was stored in the same area:  a) Rear warehouse building: On or about December 6, 2024, employees were exposed to fire hazards due to a mixture of Category 2, Category 3, and Category 4 flammable liquids being stored in a manner not in accordance with Table H-14.  b) Rear warehouse building: On or about December 6, 2024, employees were exposed to fire hazards due to a mixture of Category 2, Category 3, and Category 4 flammable liquids being stored in the same area as combustible materials such as but not limited to cardboard.  Abatement certification is required.
Recent events (2)
  • — I (S) $5200
  • — Z (S) $8276

1910.106 D05 VI F

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 14, 2025
Abate by
Mar 28, 2025
Penalty
Initial $8,276 · Current $5,200 Reduced
29 CFR 1910.106(d)(5)(vi)(f): The employer did not ensure that aisleways of at least three feet were maintained to provide access to doors, windows, and standpipes:  a) Rear warehouse building: On or about December 6, 2024, employees were exposed to fire hazards in an outside flammable storage warehouse due to aisleways that provided access to an emergency exit being less than three feet in width.  Abatement certification is required.
Recent events (2)
  • — I (S) $5200
  • — Z (S) $8276

1910.106 D07 IV

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 14, 2025
Abate by
Feb 27, 2025
Penalty
Initial $8,276 · Current $5,200 Reduced
29 CFR 1910.106(d)(7)(iv): Materials which react with water were stored in the same room with flammable liquids:  a) Rear warehouse building: On or about December 6, 2024, employees were exposed to fire hazards due to storing materials reactive to water, such as, but not limited to, sodium and sodium naphthalene dispersion with flammable liquids such as, but not limited to, ethyl alcohol, reclaimed methanol, acetone, isopropanol 99%, and diethylene glycol dimethyl ether.  Abatement certification is required.
Recent events (2)
  • — I (S) $5200
  • — Z (S) $8276

1910.134 G01 I A

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 14, 2025
Abate by
Feb 27, 2025
Penalty
Initial $9,931 · Current $6,000 Reduced
29 CFR 1910.134(g)(1)(i)(A): Respirators with tight-fitting facepieces were worn by employees who had facial hair that came between the sealing surface of the facepiece and the face or that interfered with valve function:  a) Batch Processing: On or about December 6, 2024, an employee was exposed to inhalation hazards while wearing a tight-fitting respirator due to the employee having facial hair, which interfered with the valve function.  Abatement certification is required.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $9931

1910.305 G01 IV D

Serious Gravity 1 1 instance 6 exposed
Issued
Feb 14, 2025
Penalty
Initial $4,220 · Current $2,400 Reduced
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces:  a) Small parts - dryer: On or about December 6, 2024, employees were exposed to shock hazards due to an extension cord that was attached to the building surface with zip ties.  Corrected during inspection.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4220

1910.305 G01 IV A

Serious Gravity 1 1 instance 6 exposed
Issued
Feb 14, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Small parts - dryer: On or about December 6, 2024, employees were exposed to shock hazards due to an extension cord that was used to power a fan for more than 6 months.  Corrected during inspection.