Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. DEPT OF VETERAN AFFAIRS- VENTURA VET CENTER, READJUSTMENT COUNSELING SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. DEPT OF VETERAN AFFAIRS- VENTURA VET CENTER, READJUSTMENT COUNSELING SERVICE in 790 EAST SANTA CLARA STREET, SUITE 100, VENTURA, CA 93001 (NAICS 923140). OSHA activity number 347933681.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Dept of Veteran Affairs- Ventura VET Center, Readjustment Counseling Service — free Get an email when a new federal OSHA severe-injury report for U.S. Dept of Veteran Affairs- Ventura VET Center, Readjustment Counseling Service is published. One employer, no account, unsubscribe in one click.
Site address
790 EAST SANTA CLARA STREET, SUITE 100
City
VENTURA
State
CA
ZIP
93001
Mailing
790 EAST SANTA CLARA STREET, VENTURA, CA 93001
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923140
Employees
4
Ownership type
D

4 citations on file for this inspection.

1910.305 A02 IX

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 27, 2025
Abate by
Mar 7, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lamp holder with a guard  IT Closet: On or about December 11, 2024, and at times prior thereto, the lamp used for general illumination was not protected with a suitable fixture or guard. This condition potentially exposes employee(s) to fire and/or electrical hazard(s).
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 4 exposed
Issued
Jan 27, 2025
Abate by
Feb 28, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  Records Room: On or about December 11, 2024, and at times prior thereto, the Xerox VersaLink B405 fax machine was plugged into a wall outlet that was not provided with an approved faceplate cover. Employee(s) were potentially exposed to electrical and/or fire hazard(s).
Recent events (1)
  • — Z (S) $0

1910.303 B02

Repeat Gravity 5 3 instances 4 exposed
Issued
Jan 27, 2025
Abate by
Jun 13, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about December 11, 2024, and at times prior thereto, electrical equipment such as coffee makers, microwaves, and refrigerators were not used in accordance with instructions included in the listing or labeling. In the following locations: a) Main lobby, a DeLonghi coffee maker and crystal mountain water machine was plugged into a Belkin relocatable power tap.  b) Employee Breakroom, General Electric Co microwave was plugged into a Belkin SurgeMaster relocatable power tap.  c) IT closet, A triplite relocatable power tap model no. TLP606B was plugged into a Woods relocatable power tap model 6953 A1.  This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).  U.S Department of Veteran Affairs was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR  1910.303(b)(2), which was contained in OSHA inspection number 1716623, citation number 2, item number 3 and was affirmed as a final order on February 1st, 2024, with respect to a workplace located at 10535 Hospital Way Mather, CA 95655.
Recent events (2)
  • — P (R) $0
  • — Z (R) $0

1910.305 G01 IV A

Repeat Gravity 5 2 instances 4 exposed
Issued
Jan 27, 2025
Abate by
Jun 13, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about December 11, 2024, and at times prior thereto, flexible cords were used as a substitute for fixed wiring of a structure. In the following locations: a) Records room, a HP Color Laser Jet Management Printer was plugged into a yellow extension cord. b) Break room, a white refrigerator, model number 243.6580250A was plugged into an orange extension cord.   Employee(s) were potentially exposed to electrical hazard(s).  U.S Department of Veteran Affairs was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR  1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 1716623, citation number 2, item number 5 and was affirmed as a final order on February 1st, 2024, with respect to a workplace located at 10535 Hospital Way Mather, CA 95655.
Recent events (2)
  • — P (R) $0
  • — Z (R) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347933681.