OSHA Inspection: NEPW LOGISTICS, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of NEPW LOGISTICS, INC. in 16 PARKWAY DRIVE, SCARBOROUGH, ME 04070 (NAICS 322299). OSHA activity number 347942427.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nepw Logistics, INC. — free Get an email when a new federal OSHA severe-injury report for Nepw Logistics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
16 PARKWAY DRIVE
City
SCARBOROUGH
State
ME
ZIP
04070
Mailing
70 QUARRY ROAD, PORTLAND, ME 04101
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322299
Employees
40
Ownership type
A

6 citations on file for this inspection.

1910.219 F03

Serious Gravity 5 1 instance 3 exposed
Issued
Jan 24, 2025
Abate by
Mar 13, 2025
Penalty
Initial $9,949 · Current $5,969 Reduced
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven 7 feet or less above floors or platforms were not enclosed:  Wrap Machine - Employees were exposed to an unguarded chain and sprocket at foot height on the wrap machine.
Recent events (2)
  • — I (S) $5969.4
  • — Z (S) $9949

1910.305 B01 II

Serious Gravity 1 4 instances 20 exposed
Issued
Jan 24, 2025
Penalty
Initial $5,969 · Current $3,581 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  Establishment - Unused conduit openings in the following electrical equipment was not effectively closed with knockouts.    a. 220 volt electrical junction box between loading doors 5-6 b. Baler #2 electrical control box c. Electric control/junction box at the end of the wrap machine d. Open conduit into the air compressor 220 volt knife switch
Recent events (2)
  • — I (S) $3581.4
  • — Z (S) $5969

1910.303 B02

Other-than-serious 1 instance 4 exposed
Issued
Jan 24, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Loading Area Compressor - An Ingersoll Rand compressor was powered by 10-2 non-metallic sheathing which had the following discrepancies:  a. The non-metallic sheathing must be used in enclosed spaces (walls) or protected with conduit.   b. The non-metallic sheathing must follow the wall surface per NEC 336-10-A. c. The power cord must be secured within 12 inches of the junction box into the compressor per NEC 336-15.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G02 I

Other-than-serious 1 instance 5 exposed
Issued
Jan 24, 2025
Abate by
Mar 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  Wrap Line Conveyor - Electrical enclosure/wireway part number CWSC824NK had exposed electrical lines due to damaged or missing conduit on four separate sets of electrical lines entering the wireway.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 1 instance 10 exposed
Issued
Jan 24, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  In the Truck Loading Dock between doors 9-10, there was one 4x4-inch junction box with a live 220-volt electrical wire that did not have a cover.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 4 instances 20 exposed
Issued
Jan 24, 2025
Abate by
Mar 13, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Establishment - Extension cords permanently powered auto drain devices attached to air compressors in the following instances:  a. Two air compressors against the wall adjacent to the winding department.  b. Air compressors and airlines in the mechanical pit next to the wrapping machine.