OSHA Inspection: TAMPA ELECTRIC COMPANY

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of TAMPA ELECTRIC COMPANY in FOUNTAIN SQUARE 4301 ANCHOR PLAZA PARKWAY, TAMPA, FL 33634 (NAICS 221112). OSHA activity number 347964983.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tampa Electric Company — free Get an email when a new federal OSHA severe-injury report for Tampa Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
FOUNTAIN SQUARE 4301 ANCHOR PLAZA PARKWAY
City
TAMPA
State
FL
ZIP
33634
Mailing
PO BOX 111, TAMPA, FL 33601
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
221112
Employees
2000
Ownership type
A

2 citations on file for this inspection.

1910.269 L01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 25, 2025
Abate by
Jul 22, 2025
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.269(l)(1)(i): Unqualified employees were permitted to work on or with exposed energized lines or parts of equipment.  a) On or about January 7, 2025, an unqualified employee was exposed to a 7,200-volt electrical hazard when connecting and removing a transmitter signal clamp on a 600-amp gang switch.
Recent events (2)
  • — C (S) $16550
  • — Z (S) $16550

1910.269 L02 I E

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 25, 2025
Abate by
Jul 22, 2025
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.269(l)(2)(i)(E): 29 CFR  1910.269(l)(2)(i)(E): at least two employees were not present while exposing an employee to electrical hazards greater than, or equal to, the electrical hazards posed by operations listed specifically in paragraphs (l)(2)(i)(A) through (l)(2)(i)(D) of this section.   a) On or about January 7, 2025, the employer did not provide at least two employees while working on or around an open live front switch gear which exposed an employee to a 7,200-volt electrical hazard.
Recent events (2)
  • — C (S) $16550
  • — Z (S) $16550