AUSTIN, TX —
OSHA Inspection: CIRCLE K STORES INC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CIRCLE K STORES INC in 4602 EAST STASSNEY LANE, AUSTIN, TX 78744 (NAICS 445120). OSHA activity number 347965683.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CIRCLE K STORES INC
- Site address
- 4602 EAST STASSNEY LANE
- City
- AUSTIN
- State
- TX
- ZIP
- 78744
- Mailing
- 935 E. TALLMADGE AVENUE, AKRON, OH 44310
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445120
- Employees
- 9
- Ownership type
- A
Citations
10 citations on file for this inspection.
1910.157 C01
- Issued
- Jun 27, 2025
- Abate by
- Jul 24, 2025
- Penalty
- Initial $10,403 · Current $8,322 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. On or about February 21, 2025, and at times prior thereto, in the back office; a fire extinguisher was not mounted, located and identified for ready accessibility by employees.
Recent events (2)
- — I (O) $8322.4
- — Z (S) $10403
1910.157 C04
- Issued
- Jun 27, 2025
- Abate by
- Jul 24, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition. On or about February 21, 2025, and at times prior thereto, in the bathroom hallway; employees working in the convenience store were provided a fire extinguisher that was not fully charged.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.157 E02
- Issued
- Jun 27, 2025
- Abate by
- Jul 24, 2025
- Penalty
- Initial $10,403 · Current $8,322 Reduced
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly. On or about February 21, 2025, and at times prior thereto, the employer had not ensured that fire extinguishers had been visually inspected in monthly intervals.
Recent events (2)
- — I (O) $8322.4
- — Z (S) $10403
1910.157 E03
- Issued
- Jun 27, 2025
- Abate by
- Jul 24, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check. On or about February 21, 2025, and at times prior thereto, the employer had not ensured that fire extinguishers had received an annual maintenance check.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Jun 27, 2025
- Penalty
- Initial $10,403 · Current $8,322 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, outlet boxes and fittings were not provided with covers approved for the purpose. (a) On or about January 13, 2025, and at times prior thereto, employees were working at register one, and storing items beneath it, where an electrical pull box cover was missing. (b) On or about January 13, 2025, and at times prior thereto, employees were storing items near an electrical outlet with a faceplate missing.
Recent events (2)
- — I (S) $8322.4
- — Z (S) $10403
1910.1200 G08
- Issued
- Jun 27, 2025
- Penalty
- Initial $10,403 · Current $10,403
General-duty citation text
29 CFR 1910.1200(g)(8): The employer did not ensure that Safety Data Sheets were readily accessible during each work shift to employees when they were in their work area(s). On or about January 13, 2025, and at times prior thereto, employees cleaning gasoline spills and using cleaning products such as, but not limited to, VIVX Graffiti Remover and Goo Gone Goo & Adhesive Remover, did not have access to the safety data sheets.
Recent events (2)
- — I (O) $10403
- — Z (S) $10403
1910.1200 H01
- Issued
- Jun 27, 2025
- Penalty
- Initial $10,403 · Current $0 Reduced
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: On or about January 13, 2025, and at times prior thereto, employees using cleaning products such as, but not limited to, VIVX Graffiti Remover and Goo Gone Goo & Adhesive Remover were not provided training on the associated hazards of these chemicals.
Recent events (2)
- — I (S) $0
- — Z (S) $10403
1910.36 D01
- Issued
- Jun 27, 2025
- Penalty
- Initial $65,027 · Current $65,027
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: On or about January 13, 2025, and times prior thereto, an emergency exit door was locked in the closed position, requiring a key or tool to open the exit door. The Circle K Stores Inc was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.36(d)(1), which was contained in OSHA inspection number 1528309, citation number 1, item number 1, and was affirmed as a final order on August 11, 2021, with respect to a workplace located at 1205 N Market St, Sparta, IL 62286.
Recent events (2)
- — I (S) $65027
- — Z (R) $65027
1910.37 A03
- Issued
- Jun 27, 2025
- Penalty
- Initial $91,025 · Current $0 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) On or about January 13, 2025, and at times prior thereto, the storage room emergency exit door was obstructed. (b) On or about January 13, 2025, and at times prior thereto, the cooler storage emergency exit door was obstructed. The Circle K Stores Inc was previously cited for a repeat violation of this occupational safety and health standard or its equivalent standard 1910.37(a)(3), which was contained in OSHA inspection number 1528309, citation number 2 , item number 1 and was affirmed as a final order on August 11, 2021, with respect to a workplace located at 1205 N Market St, Sparta, IL 62286.
Recent events (2)
- — I (S) $0
- — Z (R) $91025
1910.303 G01
- Issued
- Jun 27, 2025
- Penalty
- Initial $65,027 · Current $65,027
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. On or about January 13, 2025, and times prior thereto, the electrical panels in the back storage room were obstructed from safe and ready access. The Circle K Stores Inc was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.303(g)(1), which was contained in OSHA inspection number 1773282, citation number 1 , item number 2, and was affirmed as a final order on December 2, 2024, with respect to a workplace located at 1606 North Main Street, Normal, IL 61761.
Recent events (2)
- — I (S) $65027
- — Z (R) $65027
More inspections at Circle K Stores INC
View Circle K Stores INC's full OSHA safety record →
More inspections in this industry (NAICS 445120)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347965683.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.