OSHA Inspection: PENNANT INGREDIENTS, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PENNANT INGREDIENTS, INC. in 235 BUFFALO ROAD, ROCHESTER, NY 14611 (NAICS 423850). OSHA activity number 347981581.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pennant Ingredients, INC. — free Get an email when a new federal OSHA severe-injury report for Pennant Ingredients, INC. is published. One employer, no account, unsubscribe in one click.
Site address
235 BUFFALO ROAD
City
ROCHESTER
State
NY
ZIP
14611
Mailing
64 CHESTER STREET, ROCHESTER, NY 14611
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423850
Employees
50
Ownership type
A

5 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 19, 2025
Abate by
Mar 13, 2025
Penalty
Initial $11,585 · Current $8,689 Reduced
29 CFR  1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them:  a) On or about 01/15/2025, in the Helio Jet Utility Room; where a maintenance mechanic cut into energized conductors (480 volts AC) while attempting to remove an obsolete air dryer. The conductors were energized (480 volts AC) and the energy isolating device used to control the circuit was neither turned off nor locked in the off position. Employee was exposed to electrical burns.   ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
  • — I (S) $8688.75
  • — Z (S) $11585

1910.333 B02 IV B

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 19, 2025
Abate by
Mar 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.333(b)(2)(iv)(B): Before circuits or equipment were worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were deenergized:  a) On or about 01/15/2025, in the Helio Jet Utility Room; where a maintenance mechanic cut into energized conductors (480 volts AC) while attempting to remove an obsolete air dryer. The mechanic was not trained to the "qualified" level and no "qualified" person tested the wiring for voltage before the mechanic cut into the conductors.  ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 19, 2025
Abate by
Mar 13, 2025
Penalty
Initial $11,585 · Current $8,689 Reduced
29 CFR  1910.332(b)(1):Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  a) On or about 01/15/2025 throughout the facility; where a maintenance technician who had not yet been trained in the company's electrical safety training, was performing work on energized electrical equipment. While attempting to remove electrical conductors and electrical conduit in the Helio Jet Utility Room, the employee cut into live, energized electrical conductors causing an electric arc flash.  ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
  • — I (S) $8688.75
  • — Z (S) $11585

1910.137 C02 VIII

Other-than-serious 1 instance 4 exposed
Issued
Feb 19, 2025
Abate by
Mar 13, 2025
Penalty
Initial $790 · Current $593 Reduced
29 CFR  1910.137(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5:  a) On or about 01/16/2025 in the maintenance shop; where electrical protective gloves were last tested in March 2022.  ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
  • — I (O) $592.5
  • — Z (O) $790

1910.146 C02

Other-than-serious 1 instance 4 exposed
Issued
Feb 19, 2025
Abate by
Mar 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.146(c)(2):The employer did not inform exposed employees, by posting danger signs or by any other equally effective means, of the existence and location of and the danger posed by the permit spaces:  a) On or about 02/05/2025 in the production area; where the 250 gallon mixing tanks were not identified in the company PRCS program, or by marking on the vessels.                       NOTE: A sign reading DANGER-PERMIT-REQUIRED CONFINED SPACE, DO NOT ENTER or using other similar language would satisfy the requirement for a sign.  ABATEMENT CERTIFICATION REQUIRED