CONESVILLE, OH —
OSHA Inspection: 500 N 4TH STREET LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of 500 N 4TH STREET LLC in 47201 CO RD 273, CONESVILLE, OH 43811 (NAICS 518210). OSHA activity number 347990483.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- 500 N 4TH STREET LLC
- Site address
- 47201 CO RD 273
- City
- CONESVILLE
- State
- OH
- ZIP
- 43811
- Mailing
- 551 MADISON AVENUE, STE 450, NEW YORK, NY 10022
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 518210
- Employees
- 10
- Ownership type
- A
Citations
7 citations on file for this inspection.
1903.19 C01
- Issued
- Sep 19, 2025
- Abate by
- Oct 24, 2025
- Penalty
- Initial $930 · Current $930
General-duty citation text
29 CFR 1903.19(c)(1): Within 10 calendar days after the abatement date, the employer must certify to OSHA (the Agency) that each cited violation has been abated, except as provided in paragraph (c)(2) of this section. a. For Citation 1, Item 1a issued on 4/30/2025, with an abatement date of 5/12/2025, the employer failed to submit certification of abatement of this violation to OSHA. b. For Citation 1, Item 2b issued on 4/30/2025, with an abatement date of 5/20/2025, the employer failed to submit certification of abatement of this violation to OSHA. c. For Citation 1, Item 2c issued on 4/30/2025, with an abatement date of 5/20/2025, the employer failed to submit certification of abatement of this violation to OSHA.
Recent events (1)
- — Z (O) $930
1910.157 C01
- Issued
- Apr 30, 2025
- Abate by
- May 12, 2025
- Penalty
- Initial $6,620 · Current $6,620
General-duty citation text
29 CFR 1910.157(c)(1):The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury. a. On or about January 27, 2025, located at 47201 County Road 273, Conesville, Ohio 43811, portable fire extinguishers located on every other transformer pad were not mounted or identified to ensure they were readily accessible to the employees. As a result, employees were exposed to electrical fire hazards.
Recent events (1)
- — Z (S) $6620
1910.157 E02
- Issued
- Apr 30, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2):Portable extinguishers or hose used in lieu thereof under paragraph (d)(3) of this section shall be visually inspected monthly. a. On or about January 27, 2025, located at 47201 County Road 273, Conesville, Ohio 43811, the employer did not ensure that the fire extinguishers on the jobsite were visually inspected monthly.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Apr 30, 2025
- Penalty
- Initial $8,276 · Current $8,276
General-duty citation text
29 CFR 1910.303(b)(2):Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. a. On or about January 27, 2025, located at 47201 County Road 273, Conesville, Ohio 43811, the employer used extension cords to supply 240 VAC to the heat trace lines for the water lines. The cords were rated for single phase 120 VAC applications in accordance with the manufacturers instructions. As a result, the employees were exposed to an electrical shock hazard.
Recent events (1)
- — Z (S) $8276
1910.304 B03 II B
- Issued
- Apr 30, 2025
- Abate by
- May 20, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(B):Receptacles other than 125 volt, single-phase, 15-, 20-, and 30-ampere receptacles that are not part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel. a. On or about January 27, 2025, located at 47201 County Road 273, Conesville, Ohio 43811, the employer used extension cords to supply 240 VAC to the heat trace lines for the water lines. The receptacles were exposed to wet outdoor conditions and did not have ground-fault circuit-interrupter (GFCI) protection. As a result, the employees were exposed to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1910.305 J02 VI
- Issued
- Apr 30, 2025
- Abate by
- May 20, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(vi):A receptacle installed in a wet location where the product intended to be plugged into it is not attended while in use (for example, sprinkler system controllers, landscape lighting, and holiday lights) shall have an enclosure that is weatherproof with the attachment plug cap inserted or removed. a. On or about January 27, 2025, located at 47201 County Road 273, Conesville, Ohio 43811, the employer used extension cords to supply 240 VAC to the heat trace lines for the water lines. The receptacles were exposed to wet outdoor conditions and did not have a suitable enclosure. As a result, the employees were exposed to an electrical shock hazard.
Recent events (1)
- — Z (S) $0
1910.178 L06
- Issued
- Apr 30, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(6):Certification. The employer shall certify that each operator has been trained and evaluated as required by this paragraph (l). The certification shall include the name of the operator, the date of the training, the date of the evaluation, and the identity of the person(s) performing the training or evaluation. a. On or about January 27, 2025, located at 47201 Co Rd 273, Conesville, Ohio, 43811: the employer did not certify that employees had been trained and evaluated on the knowledge and skills need it to operate the JLG all-terrain forklift, model 6042 T4F, serial number 0160078083.
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 518210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347990483.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.