FORT MYERS, FL —
OSHA Inspection: OVERALL OUTDOOR AND MARINE SERVICES
Monitoring inspection · Safety discipline
At a glance
On , OSHA opened a monitoring safety inspection of OVERALL OUTDOOR AND MARINE SERVICES in 5940 YOUNGQUIST ROAD, FORT MYERS, FL 33912 (NAICS 713930). OSHA activity number 348042763.
Where did this inspection happen?
- Establishment
- OVERALL OUTDOOR AND MARINE SERVICES
- Site address
- 5940 YOUNGQUIST ROAD
- City
- FORT MYERS
- State
- FL
- ZIP
- 33912
- Mailing
- 5940 YOUNGQUIST ROAD, FORT MYERS, FL 33912
What kind of inspection was it?
- Inspection type
- Monitoring (D)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 713930
- Employees
- 16
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 G01
- Issued
- Penalty
- Initial $2837.00 · Current $1702.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: (a) In the workshop located at 5940 Youngquist Rd, Fort Myers, FL 33912 on or about 2/13/25 employees were exposed to electrical shock and burn hazards, in that, electrical panels were blocked and did not have a minimum clearance of 36 inches.
Recent events (2)
- — I (S) $1702.2
- — Z (S) $2837
1910.303 F02
- Issued
- Penalty
- Initial $2837.00 · Current $1702.00 Reduced
General-duty citation text
29 CFR 1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) In the workshop located at 5940 Youngquist Rd, Fort Myers, FL 33912 on or about 2/13/25 employees were exposed to electrical shock and burn hazards, in that, the breakers in the electrical service panel were not legibly marked.
Recent events (2)
- — I (S) $1702.2
- — Z (S) $2837
1910.305 B01 I
- Issued
- Penalty
- Initial $2837.00 · Current $1702.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i):Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: (a) In the workshop located at 5940 Youngquist Rd, Fort Myers, FL 33912 on or about 2/13/25 employees were exposed to electrical shock and burn hazards, in that, conduit was separated from its fitting resulting in the exposure and potential for abrasion of inner conductors.
Recent events (2)
- — I (S) $1702.2
- — Z (S) $2837
1910.305 B01 II
- Issued
- Penalty
- Initial $2837.00 · Current $1702.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii):Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) In the workshop located at 5940 Youngquist Rd, Fort Myers, FL 33912 on or about 2/13/25 employees were exposed to electrical shock and burn hazards, in that, three unused opening's on an electrical panel were not effectively closed.
Recent events (2)
- — I (S) $1702.2
- — Z (S) $2837
More inspections in this industry (NAICS 713930)
BAY CITY, MI—2026-06-24
BAY HARBOR TS LLC
TACOMA, WA—2026-06-02
WA317991541 - S & W MARINA HOLDINGS INC
MILWAUKEE, WI—2026-05-28
CENTERPOINT MARINE INC.
JACKSONVILLE, FL—2026-05-06
ST. JOHNS BOAT COMPANY
WELCOME, MD—2026-04-06
MICHAEL GEORGE
More inspections in FL
MARIANNA, FL—2026-07-13
PRIMETIME MOBILE MASONRY LLC
MELBOURNE, FL—2026-07-13
OMNIPOTENT BRANDS, LLC
QUINCY, FL—2026-07-13
WALMART
INDIAN ROCKS BEACH, FL—2026-07-10
UNKNOWN CONTRACTOR
CLEARWATER, FL—2026-07-10
ROOFTECH ROOFING & WATERPROOFING INC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348042763.