Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DACON CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DACON CORPORATION in LA PORTE RAIL AND TERMINAL 12501 TRANG RD, LA PORTE, TX 77571 (NAICS 221122). OSHA activity number 348053117.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Dacon Corporation — free Get an email when a new federal OSHA severe-injury report for Dacon Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
DACON CORPORATION
Site address
LA PORTE RAIL AND TERMINAL 12501 TRANG RD
City
LA PORTE
State
TX
ZIP
77571
Mailing
1300 UNDERWOOD ROAD, DEER PARK, TX 77536
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
480
Ownership type
A

3 citations on file for this inspection.

1910.269 C03 II

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Apr 11, 2025
Penalty
Initial $16,550 · Current $0 Reduced
29 CFR  1910.269(c)(3)(ii): Additional job briefings were not held when significant changes occurred during the course of the work, affecting the safety of the employees.  a)  On or about October 13, 2024, at La Porte Rail and Terminal, employees were installing jumpers without conducting an additional job briefing when the scope of work changed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $16550

1910.269 M03 II

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Apr 11, 2025
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.269(m)(3)(ii): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy might be supplied to the particular lines and equipment were de-energized / inoperable (i.e. open) and then did not ensure that such means were tagged to indicate that employees were at work:  a) On or about October 13, 2024, at La Porte Rail and Terminal, where employees were connecting jumpers on a power line without ensuring all the switches to power the lines were deenergized and tagged.
Recent events (2)
  • — I (O) $16550
  • — Z (S) $16550

1910.269 N02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Apr 11, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.269(n)(2): For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section:  a) On or about October 13, 2024, at La Porte Rail and Terminal, where employees were connecting jumpers on a power line without deenergizing or grounding the lines.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Dacon Corporation's full OSHA safety record →