Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CONNECTICUT PHARMACEUTICAL SOLUTIONS, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CONNECTICUT PHARMACEUTICAL SOLUTIONS, LLC in 280 DIVIDEND ROAD SUITE 400, ROCKY HILL, CT 06067 (NAICS 111998). OSHA activity number 348089467.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Connecticut Pharmaceutical Solutions, LLC — free Get an email when a new federal OSHA severe-injury report for Connecticut Pharmaceutical Solutions, LLC is published. One employer, no account, unsubscribe in one click.
Site address
280 DIVIDEND ROAD SUITE 400
City
ROCKY HILL
State
CT
ZIP
06067
Mailing
280 DIVIDEND ROAD, ROCKY HILL, CT 06067
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
111998
Employees
100
Ownership type
A

4 citations on file for this inspection.

1910.147 C01

Serious Gravity 5 1 instance 10 exposed
Issued
May 6, 2025
Abate by
Jun 24, 2025
Penalty
Initial $8,276 · Current $4,138 Reduced
29 CFR  1910.147(c)(1):  The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  Kitchen:  On, or about, February 20, 2025, the employer had not developed and implemented a lockout/tagout program that included lockout procedures and training to authorized, affected and other employees.  Tasks such as, but not limited to, lubricating and cleaning/sanitizing were performed on equipment without implementing lockout procedures and providing training to employees.
Recent events (2)
  • — I (S) $4138
  • — Z (S) $8276

1910.212 A01

Serious Gravity 5 1 instance 8 exposed
Issued
May 6, 2025
Abate by
Jun 24, 2025
Penalty
Initial $8,276 · Current $4,138 Reduced
29 CFR  1910.212(a)(1):  One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  Kitchen:  On, or about, February 20, 2024, the bottom panel was not installed on the Baker Perkins Servoform Mini Depositor, Model CF21047-159, exposing the in-running nip points of the dual chain conveyor.
Recent events (2)
  • — I (S) $4138
  • — Z (S) $8276

1910.332 B01

Serious Gravity 5 1 instance 1 exposed
Issued
May 6, 2025
Abate by
Jul 15, 2025
Penalty
Initial $8,276 · Current $4,138 Reduced
29 CFR  1910.332(b)(1):  Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  Facility:  On, or about, March 26, 2025, maintenance personnel had not been trained regarding what work practices and protective equipment was required to protect them against electric shock, arc flash and arc blast hazards while performing diagnostic testing and when verifying whether or not electrical equipment was properly de-energized prior to working on circuits or equipment.
Recent events (2)
  • — I (S) $4138
  • — Z (S) $8276

1910.335 A01 I

Serious Gravity 5 1 instance 4 exposed
Issued
May 6, 2025
Abate by
Jul 15, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not provided with and were not using electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  Facility:  On, or about, March 26, 2025, personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, arc-resistant hair nets, hard hats and hearing protection was not worn by employees who performed diagnostic testing and/or who verified that electrical equipment was properly de-energized.  Abatement Note:  A pair of orange rubber gloves that appeared to be voltage rated were not marked to indicate that they met industry recognized standards for personal protective equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Connecticut Pharmaceutical Solutions, LLC's full OSHA safety record →