Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COAST GLOBAL CORP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of COAST GLOBAL CORP in 540 PEDRICKTOWN ROAD, LOGAN TOWNSHIP, NJ 08085 (NAICS 493110). OSHA activity number 348122250.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Coast Global Corp — free Get an email when a new federal OSHA severe-injury report for Coast Global Corp is published. One employer, no account, unsubscribe in one click.
Establishment
COAST GLOBAL CORP
Site address
540 PEDRICKTOWN ROAD
City
LOGAN TOWNSHIP
State
NJ
ZIP
08085
Mailing
540 PEDRICKTOWN ROAD, LOGAN TOWNSHIP, NJ 08085
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
8
Ownership type
A

5 citations on file for this inspection.

1910.253 B04 III

Serious Gravity 5 1 instance 8 exposed
Issued
May 12, 2025
Abate by
Jun 6, 2025
Penalty
Initial $3,783 · Current $2,500 Reduced
29 CFR  1910.253(b)(4)(iii):Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one hour.  a) Facility yard:  Oxygen cylinders were stored next to and chained together with fuel gas cylinders without a noncombustible barrier measuring at least 5 feet high or a separation distance of at least 20 feet on or about 3/20/25.  NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $3783

1910.101 B

Other-than-serious 1 instance 8 exposed
Issued
May 12, 2025
Abate by
Jun 6, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.101(b):The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  a) Warehouse:  A cylinder of oxygen was stored on the warehouse floor  and was not secured on or about 3/20/25.  NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT  DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 E01

Other-than-serious 1 instance 8 exposed
Issued
May 12, 2025
Abate by
Jun 6, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(e)(1):The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) would be met:  (a)Throughout the warehouse:  The employer did not develop and implement a written hazard communication program for the chemicals used by employees such as, but not limited to, oxygen, acetylene, propane and antifreeze, on or about 3/20/25.  NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 G01

Other-than-serious 1 instance 8 exposed
Issued
May 12, 2025
Abate by
Jun 6, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(g)(1):  Employers did not have a safety data sheet in the workplace for each hazardous chemical which they used:   (a)Throughout the warehouse:  The employer did not maintain safety data sheets for the chemicals used by employees such as, but not limited to, acetylene, oxygen, propane and antifreeze, on or about 3/20/25.   NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1,000.00 AS PER 29 CFR 1903.19.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 H01

Other-than-serious 1 instance 8 exposed
Issued
May 12, 2025
Abate by
Jun 27, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(h)(1):Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:  a) Warehouse  The employer did not provide training to employees that used chemicals such as, but not limited to oxygen, acetylene, propane and antifreeze, on or about 3/20/25.  NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348122250.