Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BOGGESS ELECTRIC INC.,

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BOGGESS ELECTRIC INC., in 4785 DIXIE HWY, FAIRFIELD, OH 45014 (NAICS 238210). OSHA activity number 348128794.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Boggess Electric INC., — free Get an email when a new federal OSHA severe-injury report for Boggess Electric INC., is published. One employer, no account, unsubscribe in one click.
Site address
4785 DIXIE HWY
City
FAIRFIELD
State
OH
ZIP
45014
Mailing
1240 GLENDALE MILFORD BLDG 13, CINCINNATI, OH 45215
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

5 citations on file for this inspection.

1926.405 B02

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Jun 18, 2025
Abate by
Jul 24, 2025
Penalty
Initial $5,958 · Current $2,000 Reduced
29 CFR  1926.405(b)(2):Covers and canopies. All pull boxes, junction boxes, and fittings shall be provided with covers. If metal covers are used, they shall be grounded. In energized installations each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.  a.)On or about March 24, 2025, the employer failed to ensure that energized junction boxes located on the ground level and the second level of a gut-rehab building were provided with covers. As a result, employees installing new wiring and making electrical connections were exposed to 208-volt electrocution hazards.
Recent events (2)
  • — I (O) $2000
  • — Z (S) $5958

1926.416 A01

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Jun 18, 2025
Abate by
Jul 24, 2025
Penalty
Initial $0 · Current $0
29 CFR  1926.416(a)(1): No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.    a.) On or about March 24, 2025, the employer failed to ensure that employees working in proximity to  live electrical junction box were protected from electric shock by deenergizing and grounding the circuit, or by effectively guarding it through insulation or maintaining a safe working distance. As a result, employees were exposed to electric shock hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1926.416 B01

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Jun 18, 2025
Abate by
Jul 24, 2025
Penalty
Initial $0 · Current $0
29 CFR  1926.416(b)(1): Barriers or other means of guarding shall be provided to ensure that workspace for electrical equipment will not be used as a passageway during periods when energized parts of electrical equipment are exposed.   a) On or about March 24, 2025, the employer failed to provide barriers or other means of guarding to prevent the use of workspaces containing exposed energized electrical components as passageways on the ground level and second level of a gut-rehab building. As a result, employees installing new wiring and making electrical connections were exposed to electrocution hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1926.960 G01

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Jun 18, 2025
Abate by
Jul 24, 2025
Penalty
Initial $5,958 · Current $0 Reduced
29 CFR  1926.960(g)(1): Hazard assessment. The employer shall assess the workplace to identify employees exposed to hazards from flames or from electric arcs.   a.) On or about March 24, 2025, the employer failed to conduct a hazard assessment of the workplace and identify missing covers and canopies for live-active junction boxes located on the ground level, and the second level of a gut-rehab building, live electrical junction boxes were deenergized and grounded or guarded effectively by insulation or by ensuring employees worked at a safe proximity ,   ,in that the employer exposed employees to electrocution hazards of 208V, from power coming into the building from outside pole, as employees installed new wiring, and connections within a new junction box.
Recent events (2)
  • — I (O) $0
  • — Z (S) $5958

1926.20 B02

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Jun 18, 2025
Abate by
Jul 24, 2025
Penalty
Initial $0 · Current $0
29 CFR  1926.20(b)(2): Such programs shall provide for frequent and regular inspections of the job sites, materials, and equipment to be made by competent persons designated by the employers.   a) On or about March 24, 2025, the employer failed to conduct frequent and regular inspections of the jobsite by a competent person to identify hazards, including missing covers on energized junction boxes and the lack of guarding or deenergization of live electrical components. As a result, employees working on the ground and second levels of a gut-rehab building were exposed to 208-volt electrocution hazards while installing new wiring and making electrical connections in energized junction boxes.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View Boggess Electric INC.,'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348128794.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.