Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: US POLYCHEMICAL CORP

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of US POLYCHEMICAL CORP in 584 CHESTNUT RIDGE ROAD, CHESTNUT RIDGE, NY 10977 (NAICS 325998). OSHA activity number 348148420.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Polychemical Corp — free Get an email when a new federal OSHA severe-injury report for US Polychemical Corp is published. One employer, no account, unsubscribe in one click.
Site address
584 CHESTNUT RIDGE ROAD
City
CHESTNUT RIDGE
State
NY
ZIP
10977
Mailing
584 CHESTNUT RIDGE ROAD SUITE 1, CHESTNUT RIDGE, NY 10977
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
325998
Employees
16
Ownership type
A

4 citations on file for this inspection.

1910.106 E03 IV A

Serious Gravity 5 2 instances 16 exposed
Issued
Sep 29, 2025
Abate by
Nov 3, 2025
Penalty
Initial $4,256 · Current $2,554 Reduced
29 CFR  1910.106(e)(3)(iv)(a): Emergency drainage systems were not provided to direct flammable liquid leakage and fire protection water to a safe location:   a) Storage Room:   Category 2 and Category 3 flammable chemicals (e.g., isopropyl alcohol, xylene, used in unit physical operation-type manufacturing were stored in 55-gallon drums along with 5-gallon containers (e.g., drums) containing  Category 3 flammable finished products which were manufactured in unit physical operations and emergency drainage systems were not provided; on or about 3/31/25.  b) Storage Rack System - IBC Storage Area:   Category 3 flammable finished products (e.g., STS-21 Plus) which were manufactured in unit physical operations were stored in two 275-gallon intermediate bulk containers and emergency drainage systems were not provided; on or about 3/31/25.  In addition to abatement certification, the employer is required to submit abatement documentation for this item.  Failure to comply will result in additional penalty of $ 1,000.00 as per 29 CFR 1903.19
Recent events (3)
  • — F (S) $2554
  • — C (S) $4256
  • — Z (S) $4256

1910.106 E06 II

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 29, 2025
Abate by
Oct 24, 2025
Penalty
Initial $4,256 · Current $2,554 Reduced
29 CFR  1910.106(e)(6)(ii):  Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container being electrically interconnected:  a) Plant Floor near the Dye Storage Area:    Employees were dispensing isopropyl alcohol (Category 2 - Flammable Liquid) from a 55 gallon drum into a plastic pail without the nozzle and the container being electrically interconnected; on or about 3/31/25.  In addition to abatement certification, the employer is required to submit abatement documentation for this item.  Failure to comply will result in additional penalty of $ 1,000.00 as per 29 CFR 1903.19
Recent events (3)
  • — F (S) $2554
  • — C (S) $4256
  • — Z (S) $4256

1910.106 H04 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 29, 2025
Abate by
Oct 24, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.106(h)(4)(iv)(a):  Equipment was not designed and arranged to prevent the unintentional escape of liquids and vapors and to minimize the quantity escaping in the event of accidental release:  a) Plant Floor - Near Dye Storage Area:   On or about 3/31/25, isopropyl alcohol (Category 2 - Flammable Liquid) was being dispensed by gravity from a 55-gallon drum into a 5-gallon pail using equipment that was not designed to prevent the unintentional escape of flammable liquids and vapors in the event of an accidental release (e.g., approved self-closing valve or equivalent).  In addition to abatement certification, the employer is required to submit abatement documentation for this item.  Failure to comply will result in additional penalty of $ 1,000.00 as per 29 CFR 1903.19
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.157 E03

Other-than-serious 2 instances 7 exposed
Issued
Sep 29, 2025
Abate by
Oct 17, 2025
Penalty
Initial $398 · Current $239 Reduced
29 CFR  1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  a) Outside the Storage Room for flammable chemicals:   On or about 9/25/25, a carbon dioxide fire extinguisher as last inspected in 2021 and had not been subject to an annual maintenance check.  b) Passageway between Office Area and Plant Floor:   On or about 9/25/25, a carbon dioxide fire extinguisher was last inspected in 2021 and had not been subject to an annual maintenance check.  The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19, failure to comply will result in additional penalty of $ 1,000.00.
Recent events (3)
  • — F (O) $239
  • — C (O) $398
  • — Z (O) $398

View US Polychemical Corp's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348148420.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.