OSHA Inspection: NAVFAC SOUTHWEST TRANSPORTATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAVFAC SOUTHWEST TRANSPORTATION in BLDG 477, NAVAL BASE NORTH ISLAND, CORONADO, CA 92135 (NAICS 811111). OSHA activity number 348156183.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Navfac Southwest Transportation — free Get an email when a new federal OSHA severe-injury report for Navfac Southwest Transportation is published. One employer, no account, unsubscribe in one click.
Site address
BLDG 477, NAVAL BASE NORTH ISLAND
City
CORONADO
State
CA
ZIP
92135
Mailing
M9477 3RD ST, CORONADO, CA 92135
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
9
Ownership type
D

14 citations on file for this inspection.

1910.151 C

Serious Gravity 1 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: Reference: ANSI Z358.1 Emergency Eyewash and Shower Standard: 5.1.6: Eyewashes shall be capable of delivering flushing fluid to the eyes not less than 1.5 liters per minute (0.4 gpm) for 15 minutes. If shut off valves are installed in the supply line for maintenance purposes, provisions shall be made to prevent unauthorized shut off.  Bldg 477, West end: On or about April 3, 2025, and at times prior thereto, employee(s) worked with car batteries which contained corrosive chemicals such as sulfuric acid. The plumbed eye wash station did not provide adequate water pressure when activated. This condition potentially exposed employee(s) to eye injuries to include blindness.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 C01

Other-than-serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  Bldg. 477, Outside employee restroom: On or about April 3, 2025, and at times prior thereto, a Buckeye Model 10 HI SA80 ABC fire extinguisher was not readily accessible and was blocked by Primo Water Dispenser. This condition potentially exposed employee(s) to fire hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.244 A01 II

Serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.244(a)(1)(ii): Rated load(s) of portable jack(s) were not legibly and permanently marked in a prominent location on the jack(s) by casting, stamping, or other suitable means.  Bldg 477, Tire Shop Area: On or about April 3, 2025, and at times prior thereto, employee(s) used a blue hydraulic portable jack, model no. 791-6402A that did not have permanently marked rated loads. Employee(s) were potentially exposed to crush by/ pinch hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 20, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Bldg. 477, lefthand side next to lift bay door #4: On or about April 3, 2025, and at times prior thereto, a white relocatable power tap, was plugged into a wall outlet and supplied power to a EZ coil extension cord which powered employee(s) electrical devices such as batteries. This condition potentially exposes employee(s) to electrical shock and/or fire hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Other-than-serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Bldg. 477, Tire Shop: On or about April 3, 2025, and at times prior thereto, items such as brooms, parts for a storage rack and a fan was stored within 36 inches of the circuit breaker panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 20, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  Bldg. 477, Next to weld shop: On or about April 3, 2025, and at times prior thereto, a yellow flexible cord was used as permanent power and was used to power equipment such as batteries in employee(s) tool boxes. This condition potentially exposed employee(s) to electrical-shock and/or fire hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 20, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  Bldg. 477, Tire Shop Area: On or about April 3, 2025, and at times prior thereto, a Hamilton Beach microwave was not connected so that strain relief was provided. The microwave had rubber sheathing which was pulled away from the male end of the cord exposing the inner wires. Employee(s) were potentially exposed to electrical- shock hazard(s).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.157 E02

Other-than-serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 20, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  Bldg. 477, Entire Facility: On or about April 3, 2025, and at times prior thereto, fire extinguishers had not been subject to their monthly maintenance check(s). This condition potentially exposed employee(s) to extinguisher mechanical failure to put out and/or escape incipient fire hazard(s).  Notice #1, Item #1b, 29 CFR 1910.157(e)(2) as required by 29 CFR 1960.8(b): The employer failed to visually inspect portable fire extinguishers monthly. The employer was cited for a violation of the same standard on February 12, 2024, Inspection 1728323, date March 19, 2024 of final order/settlement, and means of abatement.
Recent events (2)
  • — I (O) $0
  • — Z (R) $0

1910.157 E03

Other-than-serious Gravity 5 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 20, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  Bldg. 477, Entire Facility: On or about April 3, 2025, and at times prior thereto, fire extinguishers had not been subject to their annual maintenance check(s). This condition potentially exposed employee(s) to fire hazard(s).  Notice #1, Item #1c, 29 CFR 1910.157(e)(3) as required by 29 CFR 1960.8(b): The employer failed to conduct annual maintenance checks on their fire extinguishers. The employer was cited for a violation of the same standard on February 12, 2024, Inspection 1728323, date March 19, 2024 of final order/settlement, and means of abatement.
Recent events (2)
  • — I (O) $0
  • — Z (R) $0

1904.32 A01

Other-than-serious 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1904.32(a)(1): A review of the OSHA Log of Recordable Work-Related Injuries and Illnesses (OSHA Form 300 or equivalent) was not completed to ensure the Log was accurate and complete, and/or deficiencies were not identified and corrected at the end of each calendar year.  Administrative office: OSHA 300 Log - For calendar year 2024, section M, Injury (1), the number tallied at the bottom of the form was not accurate by year's end. 28 recordable injuries were noted, the number 29 was listed at the bottom of the form.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.36 G02

Other-than-serious 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 20, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  Bldg. 477, Tire Shop Area: On or about April 3, 2025, and at times prior thereto, the width between the tire rack, tires, and Rotary low-rise lift measured to be approximately 16 inches. This condition potentially exposed employee(s) to a narrow escape route and fire hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.101 B

Other-than-serious 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 5, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.101(b):The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tank cars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  Bldg. 477, Welding Area: On or about April 3, 2025, and at times prior thereto, one brown gas cylinder which held Argon, UN1006 gas was upright and unsecured from displacement. Employee(s) were potentially exposed to struck-by hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.176 B

Other-than-serious 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 12, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.176(b): Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse:  Bldg. 477, Tire Shop Area: On or about April 3, 2025, and at times prior thereto, car tires and golf cart tires were stored at heights of approximately 5 feet and greater. The tires were not stable and secure against sliding and collapse. This condition potentially exposed employee(s) to struck by hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 F06

Other-than-serious 1 instance 9 exposed
Issued
May 9, 2025
Abate by
Jun 12, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(f)(6):The employer used written materials, such as signs, placards, process sheets, or batch tickets in lieu of affixing labels to individual stationary process containers that failed to identify the container(s) to which they were applicable and did not convey the information required by 29 CFR 1910.1200(f)(5):  Bldg. 477, across from restroom: On or about April 3, 2025, and at times prior thereto, multiple chemicals to include transmission fluid and coolant were stored in a secondary container without a Globally Harmonized System Label. This condition potentially exposed employee(s) to chemical hazard(s).
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348156183.