Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TEXAROME ENGINEERING LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TEXAROME ENGINEERING LLC in 1585 RANCH ROAD 337, LEAKEY, TX 78873 (NAICS 424690). OSHA activity number 348163239.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Texarome Engineering LLC — free Get an email when a new federal OSHA severe-injury report for Texarome Engineering LLC is published. One employer, no account, unsubscribe in one click.
Site address
1585 RANCH ROAD 337
City
LEAKEY
State
TX
ZIP
78873
Mailing
1585 RANCH ROAD 337, LEAKEY, TX 78873
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
424690
Employees
25
Ownership type
A

5 citations on file for this inspection.

1910.147 C02 II

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 29, 2025
Penalty
Initial $6,620 · Current $5,500 Reduced
29 CFR  1910.147(c)(2)(ii): If an energy isolating device is capable of being locked out, the employer's energy control program under paragraph (c)(1) of this section shall utilize lockout, unless the employer can demonstrate that the utilization of a tagout system will provide full employee protection as set forth in paragraph (c)(3) of this section.  On or about April 7, 2025, at the Essentex plant boiler area, Lockout Tagout procedures were not implemented on a main distribution panel.
Recent events (2)
  • — I (S) $5500
  • — Z (S) $6620

1910.147 C07 III B

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 29, 2025
Penalty
Initial $6,620 · Current $0 Reduced
29 CFR  1910.147(c)(7)(iii)(B):Additional retraining was not provided whenever a periodic inspection under 29 CFR 1910.147(c)(6) revealed that there were deviations from or inadequacies in the employee's knowledge or use of the energy control procedures:  On or about April 7, 2025, on the west side of the Essentex plant, the employer did not verify the affected employee's knowledge of isolating energy controls.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6620

1910.305 B03 II

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 29, 2025
Penalty
Initial $6,620 · Current $3,500 Reduced
29 CFR  1910.305(b)(3)(ii):29 CFR  1910.305(b)(3)(ii): Boxes were not closed by a suitable cover and securely fastened in place.  A.	On or about April 7, 2025, at the Essentex plant boiler area, an electrical distribution panel cover was not securely covered.     B.	On or about April 7, 2025, at the Essentex plant boiler area, an electrical circuit breaker panel cover was not securely covered.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $6620

1910.305 G02 II

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 29, 2025
Penalty
Initial $6,620 · Current $4,500 Reduced
29 CFR  1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:  On or about April 7, 2025, on the west side of the Essentex plant, an energized electrical line was spiced.
Recent events (2)
  • — I (S) $4500
  • — Z (S) $6620

1910.305 G02 III

Serious Gravity 10 1 instance 6 exposed
Issued
Jul 29, 2025
Penalty
Initial $6,620 · Current $0 Reduced
29 CFR  1910.305(g)(2)(iii):Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  On or about April 7, 2025, at the Essentex plant boiler area, a flexible electrical cord was missing a strain relief attachment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $6620

View Texarome Engineering LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348163239.