NORTH HAVEN, CT ·
OSHA Inspection: NIKLYN CORPORATION
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of NIKLYN CORPORATION in 400 SACKETT POINT ROAD, NORTH HAVEN, CT 06473 (NAICS 332812). OSHA activity number 348185406.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NIKLYN CORPORATION
- Site address
- 400 SACKETT POINT ROAD
- City
- NORTH HAVEN
- State
- CT
- ZIP
- 06473
- Mailing
- P.O. BOX 268, DURHAM, CT 06422
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332812
- Employees
- 25
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.107 C06
- Issued
- Jul 18, 2025
- Abate by
- Feb 27, 2026
- Penalty
- Initial $8,276 · Current $4,138 Reduced
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: 400 Sackett Point Road, North Haven CT: On or about, and at times before April 16, 2025, the employer did not ensure the electrical equipment inside of the powder coating booth was approved for use in areas with ignitable residues and explosive vapors from the powder and liquid coatings applied by employees performing tasks such as (but not limited to) powder and spray coating activities.
Recent events (2)
- · I (S) $4138
- · Z (S) $8276
1910.107 H12
- Issued
- Jul 18, 2025
- Abate by
- Feb 27, 2026
- Penalty
- Initial $8,276 · Current $4,138 Reduced
General-duty citation text
29 CFR 1910.107(h)(12): Fire protection. All areas used for spraying, including the interior of the booth, were not protected by an automatic sprinklers or other approved automatic extinguishing equipment. 400 Sackett Point Road, North Haven CT: On or about, and at times before April 16, 2025, the employer did not ensure the two spray booths were equipped with automatic sprinklers or extinguishing equipment for the workers spraying flammable coatings and ignitable powders while performing tasks such as (but not limited to) powder and spray coating activities.
Recent events (2)
- · I (S) $4138
- · Z (S) $8276
1910.134 E01
- Issued
- Jul 18, 2025
- Abate by
- Sep 4, 2025
- Penalty
- Initial $6,620 · Current $3,310 Reduced
General-duty citation text
29 CFR 1910.134(e)(1):The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace: 400 Sackett Point Road, North Haven CT: On or about April 16, 2025, and at times before, the employer did not provide a medical evaluation to the employee using a half face respirator in conjunction with a positive pressure respirator hood while performing tasks such as (but not limited to) abrasive media blasting.
Recent events (2)
- · I (S) $3310
- · Z (S) $6620
1910.134 M04
- Issued
- Jul 18, 2025
- Abate by
- Sep 4, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(m)(4): Written materials required to be retained under 29 CFR 1910.134 were not made available upon request to affected employees and to the Assistant Secretary or designee for examination and copying: 400 Sackett Point Road, North Haven CT: On or about April 16, 2025, the employer did not provide records of the respirator medical evaluation and fit test for the employee required to wear a half face respirator during tasks such as (but not limited to) powder coating.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.1200 H02 I
- Issued
- Jul 18, 2025
- Abate by
- Sep 4, 2025
- Penalty
- Initial $930 · Current $465 Reduced
General-duty citation text
29 CFR 1910.1200(h)(2)(i): The employer did not provide information to the employees on the requirements of the Hazard Communication Standard 29 CFR 1910.1200: 400 Sackett Point Road, North Haven CT: On or about, and at times before April 16, 2025, the employer did not ensure training in the Hazard Communication standard was provided to employees using hazardous chemicals while performing tasks such as (but not limited to) powder and spray coating activities.
Recent events (2)
- · I (O) $465
- · Z (O) $930
More inspections in this industry (NAICS 332812)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 348185406.