Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: NIKLYN CORPORATION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of NIKLYN CORPORATION in 400 SACKETT POINT ROAD, NORTH HAVEN, CT 06473 (NAICS 332812). OSHA activity number 348185406.

Watch Niklyn Corporation — free Get an email when a new federal OSHA severe-injury report for Niklyn Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
NIKLYN CORPORATION
Site address
400 SACKETT POINT ROAD
City
NORTH HAVEN
State
CT
ZIP
06473
Mailing
P.O. BOX 268, DURHAM, CT 06422
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332812
Employees
25
Ownership type
A

5 citations on file for this inspection.

1910.107 C06

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8276.00 · Current $4138.00 Reduced
29 CFR  1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for     Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations:   400 Sackett Point Road, North Haven CT: On or about, and at times before April 16, 2025, the employer did not ensure the electrical equipment inside of the powder coating booth was approved for use in areas with ignitable residues and explosive vapors from the powder and liquid coatings applied by employees performing tasks such as (but not limited to) powder and spray coating activities.
Recent events (2)
  • — I (S) $4138
  • — Z (S) $8276

1910.107 H12

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $8276.00 · Current $4138.00 Reduced
29 CFR  1910.107(h)(12): Fire protection. All areas used for spraying, including the interior of the booth, were not protected by an automatic sprinklers or other approved automatic extinguishing equipment.   400 Sackett Point Road, North Haven CT: On or about, and at times before April 16, 2025, the employer did not ensure the two spray booths were equipped with automatic sprinklers or extinguishing equipment for the workers spraying flammable coatings and ignitable powders while performing tasks such as (but not limited to) powder and spray coating activities.
Recent events (2)
  • — I (S) $4138
  • — Z (S) $8276

1910.134 E01

Serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $6620.00 · Current $3310.00 Reduced
29 CFR  1910.134(e)(1):The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace:  400 Sackett Point Road, North Haven CT: On or about April 16, 2025, and at times before, the employer did not provide a medical evaluation to the employee using a half face respirator in conjunction with a positive pressure respirator hood while performing tasks such as (but not limited to) abrasive media blasting.
Recent events (2)
  • — I (S) $3310
  • — Z (S) $6620

1910.134 M04

Other-than-serious 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.134(m)(4): Written materials required to be retained under 29 CFR 1910.134 were not made available upon request to affected employees and to the Assistant Secretary or designee for examination and copying:  400 Sackett Point Road, North Haven CT: On or about April 16, 2025, the employer did not provide records of the respirator medical evaluation and fit test for the employee required to wear a half face respirator during tasks such as (but not limited to) powder coating.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 H02 I

Other-than-serious 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $930.00 · Current $465.00 Reduced
29 CFR  1910.1200(h)(2)(i): The employer did not provide information to the employees on the requirements of the Hazard Communication Standard 29 CFR 1910.1200:   400 Sackett Point Road, North Haven CT: On or about, and at times before April 16, 2025, the employer did not ensure training in the Hazard Communication standard was provided to employees using hazardous chemicals while performing tasks such as (but not limited to) powder and spray coating activities.
Recent events (2)
  • — I (O) $465
  • — Z (O) $930

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348185406.