Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AMERIKOA INGREDIENTS LLC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of AMERIKOA INGREDIENTS LLC. in 1899 HIGH GROVE LANE, NAPERVILLE, IL 60540 (NAICS 311423). OSHA activity number 348210097.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Amerikoa Ingredients LLC. — free Get an email when a new federal OSHA severe-injury report for Amerikoa Ingredients LLC. is published. One employer, no account, unsubscribe in one click.
Site address
1899 HIGH GROVE LANE
City
NAPERVILLE
State
IL
ZIP
60540
Mailing
1899 HIGH GROVE LANE, NAPERVILLE, IL 60540
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311423
Employees
7
Ownership type
A

3 citations on file for this inspection.

1910.37 B06

Other-than-serious 2 instances 7 exposed
Issued
May 16, 2025
Abate by
Jun 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.37(b)(6):Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted.  a) On or about April 30, 2025 the employer did not ensure that the Exit sign on the office door was illuminated, thereby exposing employees to fire hazards.  b) On or about April 30, 2025 the employer did not ensure  that the Exit sign on the main employee door was illuminated, thereby exposing employees to fire hazards.
Recent events (1)
  • — Z (O) $0

1910.157 C01

Other-than-serious 1 instance 7 exposed
Issued
May 16, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(1):The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.  On or about April 30, 2025 the employer did not ensure that the fire extinguisher mounted on the north side in Building 4, across the battery charging area, was unobstructed, thereby exposing employees to fire hazards.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 7 exposed
Issued
May 16, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:(a) (LOCATION) (IDENTIFY EQUIPMENT AND CONDITION(S)) (STATE HAZARD(S) TO EMPLOYEE(S))  On or about April 30, 2025 the employer did not ensure that the electrical panel in building 1, across from the drive-in dock, was unobstructed, thereby exposing employees to electrical hazards.
Recent events (1)
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348210097.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.