OSHA Inspection: XPRESS NATURAL GAS, LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of XPRESS NATURAL GAS, LLC in 3814 NORTH ROAD, MONTROSE, PA 18801 (NAICS 221210). OSHA activity number 348314964.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Xpress Natural GAS, LLC — free Get an email when a new federal OSHA severe-injury report for Xpress Natural GAS, LLC is published. One employer, no account, unsubscribe in one click.
Site address
3814 NORTH ROAD
City
MONTROSE
State
PA
ZIP
18801
Mailing
300 SOUTH GRAND AVENUE SUITE 4100, LOS ANGELES, CA 90071
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
221210
Employees
21
Ownership type
A

4 citations on file for this inspection.

1910.132 A

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 15, 2025
Abate by
Jan 12, 2026
Penalty
Initial $8,513 · Current $8,513
29 CFR 1910.132(a): Protective equipment was not used when necessary whenever hazards capable of causing injury and impairment were encountered:  a) Compressor Area and Fill Bays: On or about December 5, 2025, an employee was exposed to a potential flash fire hazard while operating the natural gas compressors and filling trailers with compressed natural gas, and the employer did not ensure that the employee wore flame-resistant (FR) bodily protection.  ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — C (S) $8513
  • — Z (S) $8513

1910.119 E01

Serious Gravity 10 1 instance 21 exposed
Issued
Dec 15, 2025
Abate by
Apr 29, 2026
Penalty
Initial $11,916 · Current $11,916
29 CFR  1910.119(e)(1): The employer did not perform an initial process hazard analysis (hazard evaluation) on processes covered by 29 CFR 1910.119:  a) Compressor Area and Fill Bays: On or about June 16, 2025, the employer did not perform an initial process hazard analysis (PHA) to identify, evaluate and control hazards for the compressing of natural gas, transfer of natural gas, filling of trailers with compressed natural gas, and staging/storage of trailers filled with compressed natural gas, a process involving over 10,000 pounds of a Category 1 flammable gas.  ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED
Recent events (2)
  • — C (S) $11916
  • — Z (S) $11916

1910.119 F01

Serious Gravity 10 1 instance 21 exposed
Issued
Dec 15, 2025
Abate by
Apr 29, 2026
Penalty
Initial $11,916 · Current $11,916
29 CFR  1910.119(f)(1): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process:   a) Compressor Area and Fill Bays: On or about June 16, 2025, the employer did not develop operating procedures for the operation of the natural gas compressors and the filling of trailers with compressed natural gas, a process involving over 10,000 pounds of a Category 1 flammable gas.  ABATEMENT CERTIFICATION AND DOCUMENTATION REQUIRED
Recent events (2)
  • — C (S) $11916
  • — Z (S) $11916

1910.307 C02 I

Serious Gravity 5 2 instances 4 exposed
Issued
Dec 15, 2025
Abate by
Feb 3, 2026
Penalty
Initial $8,513 · Current $8,513
29 CFR  1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the class of location:  a) Garage: On or about June 16, 2025, employees performed maintenance on the fuel systems of compressed natural gas (CNG) vehicles, and the non-rated ceiling fan and associated electrical installations at the top of the ceiling were not approved for use in a hazardous (classified) location where flammable vapors could accumulate in the event of a release.  b) Garage: On or about June 16, 2025, employees performed maintenance on the fuel systems of compressed natural gas (CNG) vehicles, and the emergency exhaust fan and associated electrical installations on the wall were not approved for use in a hazardous (classified) location where flammable vapors would be directed toward the fan in the event of a gas detection sensor activation or release.     ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — C (S) $8513
  • — Z (S) $8513

View Xpress Natural GAS, LLC's full OSHA safety record →