COMMERCE CITY, CO —
OSHA Inspection: UNITED PARCEL SERVICE, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of UNITED PARCEL SERVICE, INC. in 5020 IVY ST, COMMERCE CITY, CO 80022 (NAICS 492110). OSHA activity number 348354374.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNITED PARCEL SERVICE, INC.
- Site address
- 5020 IVY ST
- City
- COMMERCE CITY
- State
- CO
- ZIP
- 80022
- Mailing
- 5020 IVY ST, COMMERCE CITY, CO 80022
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 492110
- Employees
- 3200
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.333 B02 II B
- Issued
- Aug 22, 2025
- Abate by
- Jul 6, 2026
- Penalty
- Initial $16,550 · Current $9,930 Reduced
General-duty citation text
1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures. (a) 5020 Ivy St, Commerce City CO: On or about July 3, 2025, the employer did not ensure that equipment, including but not limited to motor control centers (MCCs), was de-energized before work began. The company's 480V Allen-Bradley Centerline MCC were not properly locked before maintenance mechanic began removing fuse. This condition exposed employees to hazards from arch flash and arc blast.
Recent events (3)
- — F (O) $9930
- — C (S) $16550
- — Z (S) $16550
1910.269 L08 V
- Issued
- Aug 22, 2025
- Abate by
- Jul 6, 2026
- Penalty
- Initial $16,550 · Current $9,930 Reduced
General-duty citation text
29 CFR 1910.269(l)(8)(v):The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm2. This protective equipment shall cover the employee's entire body. 5020 Ivy St, Commerce City CO: On or about July 3, 2025, the employer did not ensure that each employee conducting maintenance on the 480V Allen-Bradley Centerline MCC wore protective electrical arc flash clothing.
Recent events (3)
- — F (O) $9930
- — C (S) $16550
- — Z (S) $16550
More inspections at United Parcel Service, INC.