NORWICH, CT —
OSHA Inspection: MINI MELTS USA, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of MINI MELTS USA, INC. in 19 OHIO AVENUE, NORWICH, CT 06360 (NAICS 311520). OSHA activity number 348357062.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MINI MELTS USA, INC.
- Site address
- 19 OHIO AVENUE
- City
- NORWICH
- State
- CT
- ZIP
- 06360
- Mailing
- 245 ASYLUM STREET, NORWICH, CT 06360
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311520
- Employees
- 23
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.303 G01 I A
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $6,029 · Current $4,000 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Trailer Yard: On, or about, July 7, 2025, the working space for the Eaton 480/277 volt panelboard labeled, "Parking Lot Sub Panel 1" was blocked by a concrete barrier and propane cylinder storage cage.
Recent events (2)
- — I (S) $4000
- — Z (S) $6029
1910.332 B01
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $16,550 · Current $11,000 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: Trailer Yard: On, or about, July 7, 2025, employees had not been provided with training regarding electrical safety related work practices while handling live power cord connections for the trailer freezer units.
Recent events (2)
- — I (S) $11000
- — Z (S) $16550
1910.332 B02
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety: Trailer Yard: On, or about, July 7, 2025, employees who were unqualified by training or experience to recognize and employ safety related work practices to reduce/eliminate exposure to electrical hazards had not been provided with training necessary to understand electrical hazards and to implement electrical safety related work practices.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A05 II
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(5)(ii): Energized plug and receptacle connections were handled without insulating protective equipment where the condition of the connection could provide a conducting path to the employee's hand (for example, a cord connector is wet): Trailer Yard: On, or about, July 7, 2025, an employee attempted to unplug a 480 volt land line from a trailer freezer after rain had fallen. Adequate insulating protective equipment was not used.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: Trailer Yard: On, or about, July 7, 2025, employees were not provided with adequate personal protective equipment, such as but not limited to, voltage rated gloves, when handling live electrical connections that were located outside and could become wet from the elements.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A02 I
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $10,050 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): Trailer Yard: On, or about, July 7, 2025, the employer did not implement a program to visually inspect equipment related to the land power lines for the trailer freezers. The cords and connectors were subject to damage from pedestrian and vehicular traffic.
Recent events (2)
- — I (S) $7000
- — Z (S) $10050
1910.334 A02 II
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service: Trailer Yard: On, or about, July 7, 2025, a flexible cord provided for a trailer freezer unit was damaged. The outer insulation jacket was split open exposing the inner, coated conductors.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.110 B06 VI
- Issued
- Sep 15, 2025
- Abate by
- Oct 31, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.110(b)(6)(vi): Readily ignitable material such as weeds and long dry grass was not removed within 10 feet of any container: Trailer Yard: On, or about, July 7, 2025, dried vegetation was observed under and around a storage cage for propane cylinders.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Mini Melts USA, INC.
View Mini Melts USA, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311520)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348357062.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.