DENVER, CO —
OSHA Inspection: HAMMER INTERMEDIATE CO LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of HAMMER INTERMEDIATE CO LLC in 1355 WEST 52ND AVENUE, DENVER, CO 80221 (NAICS 423140). OSHA activity number 348362476.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HAMMER INTERMEDIATE CO LLC
- Site address
- 1355 WEST 52ND AVENUE
- City
- DENVER
- State
- CO
- ZIP
- 80221
- Mailing
- 1749 MALLORY LANE SUITE 200, BRENTWOOD, TN 37027
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423140
- Employees
- 1640
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.37 B06
- Issued
- Dec 30, 2025
- Abate by
- Jan 27, 2026
- Penalty
- Initial $9,457 · Current $3,900 Reduced
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: (a) 1355 West 52nd Avenue, Denver, CO 80221: On or about July 9, 2025, the employer did not protect employees from potential fire hazards in that the exit sign adjacent to bay five was not illuminated.
Recent events (2)
- — I (S) $3900
- — Z (S) $9457
1910.106 E06 I
- Issued
- Dec 30, 2025
- Abate by
- Jan 27, 2026
- Penalty
- Initial $16,550 · Current $16,550
General-duty citation text
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: (a) 1355 West 52nd Avenue, Denver, CO 80221: On or about July 9, 2025, the employer did not protect employees from fire and explosion hazards in that employees were authorized to use spark producing electrical equipment such as hand-held battery drills to extract gasoline from automobile fuel tanks.
Recent events (2)
- — I (S) $16550
- — Z (S) $16550
1910.106 E06 II
- Issued
- Dec 30, 2025
- Abate by
- Jan 27, 2026
- Penalty
- Initial $16,550 · Current $16,550
General-duty citation text
29 CFR 1910.106(e)(6)(ii): Grounding. Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 �F (37.8 �C) were dispensed into containers and the nozzle and container were not electrically interconnected: (a) 1355 West 52nd Avenue, Denver, CO 80221: On or about July 9, 2025, the employer did not protect employees from fire and explosion hazards in that employees were authorized to transfer gasoline from automobile fuel tanks to a 55-gallon plastic drums without ensuring the the nozzle and container were electrically bonded or grounded.
Recent events (2)
- — I (S) $16550
- — Z (S) $16550
1910.305 G01 IV A
- Issued
- Dec 30, 2025
- Abate by
- Jan 27, 2026
- Penalty
- Initial $8,512 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) 1355 West 52nd Avenue, Denver, CO 80221: On or about July 9, 2025, the employer did not protect employees from electrical shock and fire hazards in that temporary flexible cord was used as permanent wiring to power an industrial fan between bays 4 and 5.
Recent events (2)
- — I (O) $0
- — Z (S) $8512
1910.305 G02 III
- Issued
- Dec 30, 2025
- Abate by
- Jan 27, 2026
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) 1355 West 52nd Avenue, Denver, CO 80221: On or about and at times prior to July 9, 2025, the employer did not protect employees from potential electrical shock in that that temporary flexible cord that was used as permanent wiring to power an industrial fan between bays 4 and 5 was damaged. The jacket was separated from the male-end connector, thus exposing the insulated wires.
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections in this industry (NAICS 423140)