Safety Incidents OSHA Severe Injury Reports · 2015–2025
3,783,325Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: ONSITE CONSTRUCTION SERVICES LLC

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ONSITE CONSTRUCTION SERVICES LLC in 1776 K STREET NW, WASHINGTON, DC 20006 (NAICS 238210). OSHA activity number 348380395.

Watch Onsite Construction Services LLC — free Get an email when a new federal OSHA severe-injury report for Onsite Construction Services LLC is published. One employer, no account, unsubscribe in one click.
Site address
1776 K STREET NW
City
WASHINGTON
State
DC
ZIP
20006
Mailing
1004 DIDMARTON DR, BOWIE, MD 20721
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
238210
Employees
60
Ownership type
A

2 citations on file for this inspection.

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $11585.00 · Current $11585.00
29 CFR  1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: (a)(LOCATION)(IDENTIFY SPECIFIC EQUIPMENT AND/OR CONDITIONS)(DESCRIBE HAZARDS WHERE NECESSARY)  a) On or about July 14, 2025, at a worksite located at 2619 Wisconsin Ave NW, Washington, DC; parking deck, The employer did not properly de-energize the switchgear while employees were running cable, which led to an electrical arc. As a result, one employee sustained electrical burns and also experienced smoke inhalation.  In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet), in addition, documentation demonstrating the abatement is complete must be included with your certification.  This documentation may include but is not limited to evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (1)
  • — Z (S) $11585

1926.416 A03

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1926.416(a)(3):The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take.  (a)(LOCATION)(IDENTIFY SPECIFIC EQUIPMENT AND/OR CONDITIONS)(DESCRIBE HAZARDS WHERE NECESSARY)  a) On or about July 14, 2025, at a worksite located at 1776 K Street NW, Washington, DC, the employer failed to develop comprehensive safety procedures and did not conduct thorough training for employees on the hazards associated with working withing an energized switchgear high-voltage equipment (480V).  They  also failed to provide proper personal protective equipment (PPE), including insulated gloves, voltage-rated tools, and arc-rated clothing. As a result of these oversights, a serious incident occurred in which an employee suffered electrical burns from an electrical flash.  In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the Certification of Corrective Action Worksheet), in addition, documentation demonstrating the abatement is complete must be included with your certification.  This documentation may include but is not limited to evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (1)
  • — Z (S) $0

MACY'S